204    HANDBOOK OF ELECTRICAL ENGINEERING

              Table 9.18. Land based Installations. 3800/6600 V. 6350/11,000 V. 8700/15,000 V. Cu/XLPE/PVC/AWA/
              PVC single core
              Nominal     Air       Air     Ducts           Direct buried              Notes
              conductor  trefoil    3       trefoil
                     2
              area (mm )        horizontally       trefoil    3           3
                                  spaced                  horizontally  horizontally
                                                           touching     spaced
                  50      250       300      220    220      220         230     Thermal resistivity
                  70      310       370      260    270      270         280       of soil is 1.2 C
                                                                                             ◦
                                                                                   m/W
                  95      375       460      305    320      317         335     Ambient air temp. is
                                                                                     ◦
                 120      430       530      340    360      355         380       25 C
                 150      490       600      375    410      403         430     Depth of laying
                 185      550       690      410    455      445         485       cables is 0.5 m
                 240      650       820      470    520      505         560     Standard ground
                                                                                            ◦
                 300      740       940      500    580      560         640       temp. is 15 C
                 400      840      1100      530    650      620         730     Conductor surface
                                                                                            ◦
                                                                                   temp. is 90 C.
                               ◦
              Ambient air temperature C          25    30     35    40     45    50     55    60
              Rating factor K air for cables laid in air  1.0  0.96  0.92  0.88  0.84  0.79  0.73  0.68
                            ◦
              Ground temperature C               10    15     20    25     30    35     40
              Rating factor K grd for cables laid in the ground  1.03  1.0  0.97  0.93  0.89  0.86  0.82
                          Table 9.19. Land based Installations. 3800/6600 V. Cu/XLPE/PVC/AWA/PVC
                          single core Cu/XLPE/PVC/SWA/PVC three cores
                          Nominal         Single core in trefoil          3 cores
                          conductor
                                 2
                          area (mm )   Resistance   Reactance at  Resistance   Reactance
                                            ◦
                                                                       ◦
                                        at 90 C       50 Hz        at 90 C     at 50 Hz
                                       (ohm/km)      (ohm/km)     (ohm/km)     (ohm/km)
                              16                                    1.47        0.137
                              25                                    0.927       0.129
                              35                                    0.668       0.121
                              50         0.494         0.134        0.494       0.115
                              70         0.343         0.125        0.343       0.108
                              95         0.248         0.119        0.248       0.102
                             120         0.196         0.114        0.196       0.0988
                             150         0.159         0.111        0.159       0.0962
                             185         0.128         0.109        0.128       0.0931
                             240         0.098         0.105        0.098       0.0900
                             300         0.080         0.103        0.080       0.0874
                             400         0.064         0.100        0.064       0.0849


              9.4.2.2 Derating factor due to ground temperature

              Manufacturers quote current ratings of their cables laid in the ground at a particular ambient temper-
                         ◦
                                  ◦
              ature e.g., 15 C and 20 C. They also provide tables of derating factors (K grd ) based on the chosen
              ground temperature, see the above tables, and Chapter 8 of Reference 4.