Page 223 - Handbook of Electrical Engineering
P. 223

CABLES, WIRES AND CABLE INSTALLATION PRACTICES     207

           The secondary cable runs on its own cable rack to a switchboard. Both cable routes are short enough
           to neglect volt-drop considerations. Find suitable Cu/XLPE/PVC/SWA/PVC cable conductor sizes.
                 Suitable derating factors:-

           a) For air ambient temperature      K air  = 0.84
           b) For ground temperature           K grd = 0.86
           c) For grouping cables in air       K ga  = 1.00
           d) For grouping cables in the ground  K gg  = 0.65
           e) For ground thermal resistivity   K gth  = 0.75
            f) For depth of burial             K bury = 0.98
           g) For using ducts in ground        K duct = 0.875
           h) Overall derating factor for air  K a   = K air × K ga = 0.84
            i) Overall derating factor for ground  K g  = K grd × K gg × K gth × K bury × K duct
                                                     = 0.86 × 0.65 × 0.75 × 0.98 × 0.875 = 0.36

           Solution for primary cable:

           Calculate the primary current for the ONAF loading of 5 MVA.
                               5000000
           Primary current I p = √       = 262.4amps
                               3 × 11000
           Overall derating factor = K g = 0.36

                                                I p  262.4
                                    ◦
           Cable equivalent current at 25 C = I c25 =  =   = 728.9amps
                                               K g    0.36
           From Table 9.22 the nearest cable rated current equal to or greater than 728.9 amps for cables run
                                        2
           in air is 740 amps for a 400 mm 3-core cable. This choice would have a spare capacity in the
                                                                           2
           cable of only 1.5%, which is rather low for a practical design. A 400 mm high voltage cable is
           also difficult to manipulate during laying. A better choice would be two cables in parallel. The same
           overall derating factor can be used if the two cables are spaced sufficiently far apart.
                                          ◦    I c25
                 Cable equivalent current at 25 C =  per cable = 364.4amps.
                                                2
                                                                                      2
                 From Table 9.22 a suitable cable size to provide at least a 10% margin is 150 mm , giving a
           rated current in air of 430 amps. Hence the appropriate choice for the primary is 2 × 3c × 150 mm 2
           cables. The margin will allow for short duration overloading of the transformer.

                 Solution for the secondary cable:

           The corresponding secondary current
                                                  11000
                                      I s = 262.4 ×     = 418.3amps
                                                   6900
           Overall derating factor = K a = 0.84
                                                 I s  418.3
                                    ◦
           Cable equivalent current at 25 C = I c25  =  =  = 498.0amps
                                                K a   0.84
   218   219   220   221   222   223   224   225   226   227   228