Page 441 - Handbook of Electrical Engineering
P. 441

430    HANDBOOK OF ELECTRICAL ENGINEERING

              Table 15.6. Harmonic rms currents and voltages in a star-wound induction motor that is fed from a current
              source inverter
              Harmonic      Stator current     Rotor current      Magnetising       Air-gap voltage
              number                                                current

                          Mag.     Angle     Mag.     Angle     Mag.     Angle     Mag.     Angle
                         (Amps)  (Degrees)  (Amps)   (Degrees)  (Amps)  (Degrees)  (Amps)  (Degrees)
                  1      392.28      0      370.54    11.33     78.36   −68.32    229.67     21.68
                  5       78.45    180.0     75.58   180.014     2.87    179.63    42.06    269.63
                  7       56.01    180.0     53.99   180.014     2.05    179.63    42.06    269.63
                 11       35.66      0       34.35     0.007     1.30    −0.186    42.06     89.81
                 13       30.67      0       29.07     0.007     1.10    −0.186    42.06     89.81
                 17       23.07    180.0     22.23   180.005     0.84    179.88    42.06    269.88
                 19       20.65    180.0     19.89   180.005     0.76    179.88    42.06    269.88
                 23       17.05      0       16.43     0.004     0.62    −0.093    42.06     89.91
                 25       15.69      0       15.12     0.004     0.57    −0.093    42.06     89.91
                 29       13.53    180.0     13.03   180.003     0.49    179.93    42.76    269.93
                 31       12.65    180.0     12.19   180.003     0.46    179.93    42.76    269.93







































              Figure 15.13  Instantaneous voltages and currents in an induction motor supplied from a current source inverter.
   436   437   438   439   440   441   442   443   444   445   446