432    HANDBOOK OF ELECTRICAL ENGINEERING

                        Table 15.8. Protection alarms and indications for a high-voltage variable speed drive

                        Function                           Protection   Alarm    Indication
                           1.  Open circuit, short circuit and  X
                                earth faults in the rectifier
                                including the faults in the
                                rectifier including the DC
                                link
                           2.  Open circuit, short circuit and  X
                                earth faults in the inverter
                                including the cable and
                                motor
                           3.  Overcurrent due to             X
                                commutation failure in the
                                rectifier
                           4.  Overcurrent due to             X
                                commutation failure in the
                                inverter
                           5.  Undervoltage at the output of  X
                                the inverter
                           6.  Overfrequency at the output of  X
                                the inverter
                           7.  Undervoltage at the input of   X
                                the rectifier
                           8.  Enclosure over-temperatures               X
                           9.  Control system faults          X          X
                          10.  Harmonic filter faults          X          X
                          11.  Single-phase operation of the  X          X
                                motor
                          12.  Overcurrent of the motor       X          X          X
                          13.  Winding temperature of the     X          X          X
                                motor
                          14.  Winding temperature of power   X          X          X
                                transformers
                          15.  Supply line voltages                                 X
                          16.  Supply line currents                                 X
                          17.  DC link voltage                                      X
                          18.  DC link current                                      X
                          19.  Motor line voltages                                  X
                          20.  Motor line current                                   X
                          21.  Set-point frequency of inverter                      X
                          22.  Actual frequency of inverter                         X
                          23.  Motor speed                                          X



              local transformers may be sufficient to cause sensitivity in the performance of the filter with variations
              in system loading. This is less of a problem where the plant is supplied from an overhead transmission
              line, and the upstream MVA capacity is large compared with the total demand of the plant.
                    Drilling rigs and low capacity AC variable speed drives are usually six-phase systems. If these
              are known to be needed at the conceptual stage of a project then their effects on other equipment