Page 141 - Handbook of Energy Engineering Calculations
P. 141

of both the GT and—because of energy added to the GT exhaust—the steam
               turbine/generator. Overall, plant output for case 1 is increased by 5.8 MW GT
               output + 0.9 MW ST output—plant auxiliary load of 0.9 MW = 6.65 MW, or
               3.3 percent. The CC heat rate is improved 0.2 percent, or 15 Btu/kWh (14.2
               kJ/kWh). The total installed cost for the evaporative cooling system, based on

               estimates provided by contractors and staff, is $1.2 million. The incremental
               cost is $1,200,000/6650 kW = $180.45/kW for this ambient condition.
                  The effectiveness of the same system operating in less-humid conditions—

               say 95°F DB (35°C) and 40 percent RH—is much greater. In this case, the
               same  evaporative  cooler  can  reduce  inlet-air  temperature  to  75°F  DB
               (23.9°C) by increasing RH to 88 percent. Here, CC output is increased by 7
               percent, heat rate is improved (reduced) by 1.9 percent, and the incremental
               installed  cost  is  $85/kW,  computed  as  above.  As  you  can  clearly  see,  the

               effectiveness of evaporative cooling is directly related to reduced RH.
                  Water-treatment requirements must also be recognized for this Case, No. 1.
               Because  demineralized  water  degrades  the  integrity  of  evaporative-cooler

               film  media,  manufacturers  may  suggest  that  only  raw  or  filtered  water  be
               used  for  cooling  purposes.  However,  both  GT  and  evaporative-cooler
               suppliers  specify  limits  for  turbidity,  pH,  hardness,  and  sodium  (Na)  and
               potassium (K) concentrations in the injected water. Thus, a nominal increase
               in  water-treatment  costs  can  be  expected.  In  particular,  the  cooling  water

               requires  periodic  blowdown  to  limit  solids  buildup  and  system  scaling.
               Overall, the evaporation process can significantly increase a plant’s makeup-
               water  feed  rate,  treatment,  and  blowdown  requirements.  Compared  to  the

               base  case,  water  supply  costs  increase  by  $15/h  of  operation  for  the  first
               approach,  and  $20/h  for  the  second,  lower  RH  mode.  Disposal  of
               evaporative-cooler blowdown costs $l/h in the first mode, $2/h in the second.
               Evaporative cooling has little or no effect on the design of the steam turbine.


               3. Evaluate the economics of inlet-air chilling

               The effectiveness of evaporative cooling is limited by the RH of the ambient
               air.  Further,  the  inlet  air  cannot  be  cooled  below  the  wet-bulb  (WB)
               temperature of the inlet air. Thus, chillers may be used for further cooling of
               the inlet air below the wet-bulb temperature. To achieve this goal, industrial-

               grade  mechanical  or  absorption  air-conditioning  systems  are  used,  Fig.  9.
               Both consist of a cooling medium (water or a refrigerant), an energy source
   136   137   138   139   140   141   142   143   144   145   146