Page 143 - Handbook of Energy Engineering Calculations
P. 143

A centrifugal-compressor-based chiller can easily reduce the temperature
               of the GT inlet air from 95°F (35°C) to 60°F (15.6°C) DB—a level that is
               generally accepted as a safe lower limit for preventing icing on compressor
               inlet  blades—and  achieve  100  percent  RH.  This  increases  plant  output  by
               20.2 MW for GT + 2.4 MW for ST − 4.5 MW plant auxiliary load = 18.1

               MW, or 8.9 percent. But it degrades the net CC heat rate by 0.8 percent and
               results  in  a  1.5-in-(3.8-cm)-H O  inlet-air  pressure  drop  because  of  heat-
                                                     2
               exchanger equipment located in the inlet-air stream.
                  Cooling requirements of the chilling system increase the plant’s required
                                                                            3
               circulating water flow by 12,500 gal/min (47.3 m /min). Combined with the
               need  for  increased  steam  condensing  capacity,  use  of  a  chiller  may

               necessitate a heat sink 25 percent larger than the base case. The total installed
               cost  for  the  mechanical  chilling  system  for  Case  2  is  $3-million,  or  about
               $3,000,000/18,100  kW  =  $165.75/kW  of  added  output.  Again,  costs  come

               from contractor and staff studies.
                  Raw-water consumption increase the plant’s overall O&M costs by $35/h
               when  the  chiller  is  operating.  Disposal  of  additional  cooling-tower  blow-
               down costs $17/h. The compressor used in Case 2 consumes about 4 MW of
               auxiliary  power  to  handle  the  plant’s  68-million  Btu/h  (19.9  MW)  cooling

               load.


               4. Analyze an absorption chilling system
               Absorption  chilling  systems  are  somewhat  more  complex  than  mechanical
               chillers. They use steam or hot water as the cooling motive force. To achieve

               the same inlet-air conditions as the mechanical chiller (60°F DB, 100 percent
               RH) (15.6°C, 100 percent RH), an absorption chiller requires about 111,400
                                                      2
               lb/h (50,576 kg/h) of 10.3-lb/in  (gage) (70.9-kPa) saturated steam, or 6830
                                   3
               gal/min (25.9 m /min) of 370°F (188°C) hot water.
                  Cost-effective supply of this steam or hot water requires a redesign of the
               reference plant. Steam is extracted from the low-pressure (l-p) steam turbine
                              2
               at 20.3 lb/in  (gage) (139.9 kPa) and attemperated until it is saturated. In this
               case, the absorption chiller increases plant output by 8.7 percent or 17.4 MW
               but degrades the plant’s heat rate by 1 percent.
                  Although  the  capacity  of  the  absorption  cooling  system’s  cooling-water

               loop must be twice that of the mechanical chiller’s, the size of the plant’s
   138   139   140   141   142   143   144   145   146   147   148