Page 439 - Handbook of Energy Engineering Calculations
P. 439

not exceed the outlet process-stream temperature if a single body having
                  one shell pass—but more than one tube pass—is used.


               • When cooling or condensing a fluid, the inlet coolant temperature should
                  not be less than 5°C (9°F) above the freezing point of the highest freezing
                  component of the fluid.


               • For cooling reactors, a 10°C (18°F) to 15°C (27°F) difference should be

                  maintained  between  reaction  and  coolant  temperatures  to  permit  better
                  control of the reaction.


               • A 20°C (36°F) approach to the design air temperature is the minimum for
                  air-cooled  exchangers.  Economic  justification  of  units  with  smaller

                  approaches  requires  careful  study.  Trim  coolers  or  evaporative  coolers
                  should also be considered.


               • When condensing in the presence of inerts, the outlet coolant temperature
                  should be at least 5°C (9°F) below the dew point of the process stream.
                  In an exchanger having one shell pass and one tube pass, where two fluids

               may  transfer  heat  in  either  cocurrent  or  countercurrent  flow,  the  relative
               direction of the fluids affects the value of the mean temperature difference.
               This is the log mean in either case, but there is a distinct thermal advantage to

               counterflow, except when one fluid is isothermal.
                  In  concurrent  flow,  the  hot  fluid  cannot  be  cooled  below  the  cold-fluid
               outlet  temperature;  thus,  the  ability  of  cocurrent  flow  to  recover  heat  is
               limited. Nevertheless, there are instances when cocurrent flow works better,
               as  when  cooling  viscous  fluids,  because  a  higher  heat-transfer  coefficient

               may  be  obtained.  Cocurrent  flow  may  also  be  preferred  when  there  is  a
               possibility  that  the  temperature  of  the  warmer  fluid  may  reach  its  freezing
               point.

                  These factors are important in determining the performance of a shell-and-
               tube exchanger:
                  Tube Diameter, Length. Designs with small-diameter tubes [5/8 (15.8 mm)
               to 1 in (25.4 mm)] are more compact and more economical than those with
               larger-diameter  tubes,  although  the  latter  may  be  necessary  when  the

               allowable  tubeside  pressure  drop  is  small.  The  smallest  tube  size  normally
   434   435   436   437   438   439   440   441   442   443   444