Page 442 - Handbook of Energy Engineering Calculations
P. 442

4/3
                                                                         1/3
                                                    k = 0.86 (cs /M )
                  An important compound for which the Weber equation does not work well
               is  water  (the  calculated  thermal  conductivity  is  less  than  the  actual  value).
               Figure 12 gives the physical-property factor for water (as a function of fluid

               temperature)  that  is  to  be  substituted  in  the  equations  for  sensible-heat
               transfer with water, or for condensing with steam.
































                          FIGURE  12  Physical-property  factors  for  water  and  steam  vs
                     temperature. (Chemical Engineering.)


                  If the thermal conductivity is known, it is best to obtain a pseudomolecular

               weight by:
                                                                        3 4
                                                      M = 0.636(c/k) S
                  This  value  is  substituted  in  the  applicable  equation  to  solve  for  the
               physical-property factor.
                  Tube pitch for both triangular and square-pitch arrangements is assumed to
               be 1.25 times the tube diameter. This is a standard pitch used in the majority
               of shell-and-tube heat exchanges. Slight deviations do not appreciably affect

               results.
                  Shell diameter is related to the number of tubes (nN ) by the empirical
                                                                                    PT
               equation:
   437   438   439   440   441   442   443   444   445   446   447