Page 130 - Hybrid-Renewable Energy Systems in Microgrids
P. 130

114                                 Hybrid-Renewable Energy Systems in Microgrids

           grid-connected VSI is given in Fig. 7.1, where the current controllers are implemented
         in synchronous  reference frame. The operation of the inverter is regulated to inject a
         certain amount of active and reactive power, whose references are usually generated by a
         higher level controller. However, this way of controlling a VSI yields undesirable perfor-
         mance under unbalanced faults. With Park transformation, the negative-sequence compo-
         nents will appear in positive-sequence frame as signals oscillating at twice fundamental
         frequency. Due to the limited bandwidth, proportional-integral (PI) controllers result in
         imperfect tracking when the control signals accommodate such oscillations [6]. As an
         example, the short-circuit response of the system shown in Fig. 7.1 subject to a phase A-B
         fault with 0.1 Ω fault resistance is given in Fig. 7.2A, where the output current exhibit
         significant distortions under the fault. To improve the short-circuit response of the VSI
         under unbalanced faults, only positive-sequence signals are used in the control diagram
         shown Fig. 7.1. The corresponding short-circuit response to the same fault is illustrated in
         Fig. 7.2B. Even though the current is free of distortions, the peak current and the amount
         of injected power are out of control due to uncontrolled negative-sequence current. There-
         fore, a similar control loop is implemented for negative-sequence component, resulting a
         control structure in Fig. 7.3, where only positive-sequence components are used in posi-
         tive-sequence reference frame control loop and only negative-sequence components will
         appear in negative-sequence reference frame control loop. With the help of instantaneous
         power theory, the four current references can be generated in  various ways to achieve
         certain objectives. This makes the short- circuit response of the VSI significantly different
         from each other under unbalanced faults.


































         Figure 7.1  Control structure of a grid-connected VSI.
   125   126   127   128   129   130   131   132   133   134   135