Page 380 - Industrial Power Engineering and Applications Handbook
P. 380

Switchgear and controlgear assemblies 13/355
       Table 13.9  Fault currents (rms.) in a generator circuit under different fault conditions

       Sr.  Type of fault   Configuration of                 Fault currents
       no.             faulty circuit    Sub-transient       Transient          Steady state



                           r(T1                              61                  Vl   1

                                          Jr
                                         K.L
                                             xa
                                                             43  x4             fi  Xd
                        (ii) Delta connected






       2   Phase to phase   (i) Star connected




                        (ii) Delta connected
                                                             J5.x.1             Js.K.1
                                                                Jr  x;  +x2        fi  xd+x2

       3   Phase or phases  (i) Solidly grounded
           to ground
                           t--v--l



                        (ii) Impedance grounded







       Notes
       1  The above are r.m.s. values. For peak values multiply them by  &.
       2  The first peak with full asymmetry, i.e. the making current IMr will be represented by 2 (P x I,,,) (where P = factor of asymmetry as
         in Table 13.11).
       3  x2 and xo are negative and zero phase sequence reactances of the generator respectively, in n/phase.
       4 Since the ground fault currents in generators can be higher (Section 20.10.1) than the sub-transient state current, special care need be
         taken while grounding a generator to limit the ground fault current. Section 20.10.1 covers this aspect also.
       5  The relays and the breaker will operate only during the transient state, hence the significance of transient state values to set the current
         and the time of the protective and isolating devices.
       6  In certain cases, where a long delay may be necessary for the protective scheme to operate, it may be desirable to use the maximum
         steady-state short-circuit current 42 . I,, for a more appropriate setting, rather than the maximum transient current 42 . I,, as by then the
         fault current will also fall to a near steady-state value, Is,~r,,,,s,).
       x;  = 0.04 Wphase                                 = 1391 A
       x;  =0.02 Wphase                               and base reactance
        x,  = 0.015 Wphase
        x, = 0.007 Wphase                              Xb =   41 5
        I, =  1000 x 1000                                  & x 1391
             & x 415                                     = 0.17 Wphase
   375   376   377   378   379   380   381   382   383   384   385