Page 378 - Industrial Power Engineering and Applications Handbook
P. 378

Switchgear and controlgear assemblies  13/353
       Table 13.8  Typical parameters of a power generating station and its likely fault levels

       1 Generator
       Generator size (rated MVA
        x p.f.)            MW         60      67.5     110     120     200/2  10   250     500
       Approximate sub-transient
       unit reactance,     X,"(%)     15.4    17.7     15.9    13.2     16.8       16.9     17.2
       Rating              MVA        75      84.4    137.5    141.2   247        294      588
       Generator fault level,
        Isc  = (*)         kA         25.56   26.21    45.39   58.94    53.87     60.89     94.17

        [a x Is, 1         MVA       487     477      865     1072    1470       1740     3425
           x
            vr
       Rated p.f.                      0.8     0.8      0.8     0.85    0.85       0.85      0.85
       Stator nominal voltage, V,   kV   11   10.5     11      10.5     15.75      16.5     21
       Stator current (CMR)a, I,   A   3936   1639   7217     7780    3050      0 290     6 200
       Frequency, f        HZ         50      50       50      50       50        50        50
       2 Generator transformer (GT)
       Rating              MVA      75       85      140      140     250       315       500
       Impedance           Zp%       12.5f 109  12.5  f 104  12.5  f 10%  12.5f 104  14+ 10%   14.5f 10%   15* 10%
       Generator side fault level,
       considering the lower
       tolerance of impedance,   kAb   35    42      65       68      73        34        I22
       Vector group                 -                (Ynd 11)-
                                             Staddelta
                                    t---
       SPe                                                    Three-pha   two windin      3ne-phase
                                                                                          .wo-winding,
                                                                                          3  Nos 200
                                                                                          MVA each
       3 Generator isolated phase bus duct
       Rated current (CMR)a   A     4000     5000    8000     8000    10000     I2 500    I8 000
       One second short-time   kA   35       42      65       68      73        $4        I22
       rating (as for GT)~
       4 Tap-offs of the generator bus duct
       Approximate one-second kA    61       68      110      127     127       145       116
       short-time rating (rounded ofOb
       (it is the summation of
       the fault levels of the generator
       and the generator bus duct: refer to
       Figure  13.18 and a typical calculation
       in Example  13.3)
       5 Unit auxiliary transformer (UAT)
       No. of transformers                           1        1       1 or 2    I or 2    l
       Rating              MVA                       12.5     16      25 for 1   51.5 for 1   l of 25
                                                                      and       md        )r
                                                                      12.5 for 2   16 for 2   1.  of 31.5
       Impedance          Zp%                        7.5      7.5     10 for 25   10 for 31.5   LO for 25
                                                                      MVA 7.5 foi  VIVA  7.5 foi  HVA  10 for
                                                                      12.5 MVA   I6 MVA   11.5 MVA

       Vector group type            c                           Dynl or Ddo                      >
                                    <                         3-phase, 2 winding                 >
       aCMR  - Continuous maximum rating
       bThe GT HV side is connected to a power grid and the grid receives power from many sources and can have a fault level higher than that
       of G or the GT. On a fault anywhere in the main  length or the tap-offs of  the IPB between G  and the GT (Figures  13.21 and  13.18
       respectively) both generator and the grid will feed the fault (grid through the GT). The fault level of the IPB straight length may therefore
       be considered as the fault level of the grid limited upto the fault level of the GT (impedance of GT limiting the fault level). Accordingly
       we have considered the fault level of the straight length of the IPB as the fault level of the GT. It is, however, only for illustration, exact
       fault level shall depend upon the system parameters, also refer to Example 13.3 clarifying this.
       Source  NTPC and BHEL.
   373   374   375   376   377   378   379   380   381   382   383