Page 667 - Industrial Power Engineering and Applications Handbook
P. 667

19/632 Industrial Power Engineering and Applications  Handbook
        choice  of  interrupting  device  may  result  in  insulation
        failure of  the  terminal  equipment,  such  as  a  power                -Tulip
        transformer, an induction motor or interconnecting cables.               ..       contacts
        This situation may arise when:                                                    Terminal
                                                                                          bushings
        1  Interrupting small magnetizing currents, such as inter-
          rupting  an induction  motor or a transformer  on no-
          load, a situation, when the current may lag the impressed
          voltage by nearly 90".
        2  Interrupting a charged capacitor bank, when the current
          will lead the impressed voltage by  nearly 90".
        3  Interrupting an unloaded transmission or distribution
          line or a cable, Le. interrupting a line charging current,
          which is capacitive and may lead the system voltage
          by  nearly 90".                                                                 Arc  control
                                                                                          pots
        4  Interrupting  an induction motor immediately  after a
          switch on, when the current is large and highly induc-                          Moving
          tive.                                                                           contacts
        5  Interrupting  fault currents  that  are mostly  inductive
          (Section 13.4.1) and occur at very low power factors.
          They  are  excessive  in  magnitude,  and  cause high
          thermal  effects  and  electromagnetic* forces  on  the                         Oil tank
          arc chamber, the contacts and the contact mounting
          supports.

        Under  the  above  conditions,  the  arc,  as  usual,  will
        extinguish at the first current zero but will have a tendency
        to re-establish immediately again, after the current zero
        (Figure 17.1 l(c)) while the contacts are still parting. This
       is because the TRV across the parting contacts may exceed
       the dielectric strength of the contact gap achieved so far.   Figure 19.4  Rear view of  a bulk oil circuit breaker assembly
         Restoration of the dielectric strength will depend upon   showing single-break  contacts, self aligning cluster  isolating
       the speed of the moving contact and the insulating medium   contacts, terminal bushing and arc control pots (Courtesy:
        of the arc chamber. There may be a number of restrikes   GEC Alsthom)
       before a final extinction is achieved. The frequency of
        restrikes  may  be  extremely  high  (equation  (17. l)),   (70%), C2H4 (20%), CH4 (10%) and free carbon, say, 3
        depending upon the L and C of the interrupting circuit,   g per 10 litres of oil decomposed at a very high pressure
        which would have the characteristics  of a surge circuit   of 100-150  bars, in the shape of a bubble around the arc
        on formation of an arc. In terms of actual rated frequency   (Figure  19.5).  H2 is  an  extremely  good  medium  for
        (f),  restoration of the dielectric  strength may  not take   quenching and does most of the cooling of the arc plasma,
        more than one half to two cycles, i.e. 10-40 ms (for a 50   exting-uishing it while passing through it. The gases thus
        Hz system). The behaviour of circuit breaking thus depends   produced also cause turbulence in the oil in the neighbour-
        upon  the  design  and  the  quenching  medium  of  the   hood, causing rapid replacement of the oil with cool oil
       interrupting device.                           from around the contacts, thus achieving a double cooling
                                                      effect. At each current zero, it almost recovers its dielectric
                                                      strength and  also  increases  its  post-arc  resistance  as  a
        19.5  Circuit interruption in different       result  of  cooling and  arc  extinction,  making  the  inter-
             mediums                                  ruption all the more easier and complete.
                                                        Simultaneously  the bubble  also pushes  the oil  away
                                                      from around it and reduces  the cooling. Proper design,
       19.5.1  Bulk Oil Circuit Breakers (BOCBs)      however, can ensure adequate cooling during interruption
                                                      (arcing)  by  adjusting  the  speed of  the parting  contact,
       Refer to the general arrangement of this breaker in Figure   supplementing the cooling of oil through an additional
        19.4. In this device the moving contacts make and break   oil chamber, such as a side-vented explosion pot or cross
       in  an  oil  bath.  When  the  arc  is  formed  during  an   jet pot, by adjusting the gap between  the fixed and the
       interruption, the oil becomes decomposed due to excessive   moving contacts.
       heat, and produces a few gases and vapours such as H2   While breaking smaller currents, the formation of gas
                                                      may not be adequate to provide the desired cooling effect.
                                                      This  is, however, immaterial because  of  less intensive
       * The breaker  will  interrupt only during a transient state (Figure   arc  formation  requiring  much  less cooling. Extinction
       13.20) by which time the d.c. component responsible for the dynamic   may be slightly prolonged  but may be achieved by  the
       forces, has subsided.                          next current zero.
   662   663   664   665   666   667   668   669   670   671   672