Page 671 - Industrial Power Engineering and Applications Handbook
P. 671

19/636 Industrial Power Engineering and Applications  Handbook
                  Splitter or                                     Arc  plasma rising
                quenching plates                                  to the arc splitters



                                   - Housing of non
                                     magnetic material
                                     (Asbestos, bakelite,
                                     FRP or DMC etc

                                   Lengthening of
                                   arc
                                   Arc moving
                                   into arc chute




                Fixed & moving
                arcing contacts


        Figure  19.11  Process of  arc formation and  quenching in an
        ACB using splitter plates

        axial air blast through the arc plasma, when the contacts
        have just begun to separate. (See Figure  19.13(b).) The
        compressed air has greater dielectric strength and thermal
        properties than ordinary air at atmospheric pressure.
         The conventional pressure of air blast is generally 218
        to  900 lb/in2 (1.5 to  6.2 MN/m2) up to  110 kV,  up  to
        3000 lb/in2 (20.7 MN/m2 (for voltages up to 400 kV, and
        still higher pressures for higher voltages. The pressure
        requirement will change from one manufacturer to another,
        depending upon contact design, interrupting mechanism
        and design and value of resistors. Since most quenching
        is through a predetermined force of an air blast, the force
        of  arc plasma  quenching and extinction  (deionization)
        remains  the  same  for  a  particular  size  of  breaker,   a  Top terminal   e9  Compression spring
                                                      b  Moulded-plastic  base
                                                                              f2  Operating shaft
        irrespective  of  the  amount  of  current  the  interrupting   b5  Fixed contact   g1  Insulating barrier
        device may have to break. This factor inherits a tendency   d  Arc chute   g2  Insulating barrier
        to break small currents, even before their natural current   dZ Arc  runner   h4  Bimetal strip
                                                                                Intermediate shaft
        zeros, causing current chopping (Section  19.6). Current   d4  Arc splitters   h,  hs  Current transformer
                                                      d5  Leaf spring
        chopping may raise the TRV up to 2.5-3  p.u. However,   el  Moving contact   n3  Intermediate shaft
        it is possible to design these breakers to contain the value   e2  Contact carrier   n4  Magnet core
        of a TRV to a non-striking  level.            e,   Tension spring     p  Bottom terminal
         The dampening  of  a TRV  is  achieved  through  low-   e,   Flexible connector
        and high-resistance  units provided  across the  contacts.
        The low unit will short at higher TRVs and the higher unit   Figure 19.12(a)  Operating mechanism of an LTACB showing
                                                      the arc chute with splitter plates (Courtesy: Siemens)
        at lower TRVs. The arc interruption is fast and generally
        at the  first  current  zero  due  to  dampening.  When  the
        breaker is in the closed position, the resistors  are open   pressure and volume at all times. This requires an elaborate
        circuited. As soon as the main contacts begin to interrupt,   arrangement for air compression, an air storage facility,
        the contacts of resistor make first, before the main contacts   a network of feed pipes, valves and safety devices besides
        separate  and  provide  the  required  dampening. After   their regular maintenance  and upkeep. All this is costly
        extinction  of  the  arc,  the  resistor  circuit  opens  again   particularly when only a few breakers are at a particular
        automatically and restores to the original position.   installation.
         Until a few years ago these breakers  had been quite   Moreover, compressed air is released through an orifice
        common for medium voltages, up to 33 kV.  Since they   at the exhaust point at a high velocity and causes a sound
        require a powerful blast of air at high pressure and velocity   like thunder. This may  be frightening to people  in the
        into the arcing region, they require a reliable  source of   vicinity. Sub-stations involving a number of such breakers
        air supply. Air should be clean and dry and at the correct   are a nuisance to residents nearby. The larger the breaker
   666   667   668   669   670   671   672   673   674   675   676