Page 682 - Industrial Power Engineering and Applications Handbook
P. 682

Circuit interrupters 19/647
                                                      level in the arc chamber of the interrupting device, the
                                                      arc may restrike again and cause higher TRVs. This shall
                                                      further  complicates  the  process  of  interruption  and
                                                      extinction of the arc. See Blower et al. (1979), Telander
                                                      et al. (1986) and IEEE transactions  (1977).

                                                      Note
                                                      The surge frequency at which the TRV will restrike will be extremely
                                                      high. It may be of the order of  1ClOO kHz, depending upon  the
                                                      circuit constants L and C. To interrupt such high-frequency currents
                                                      is  difficult  for  an  ordinary  breaker.  But  with  the  use  of  high
                                                      technologies, such as adopted in SF6 and VCB interrupting devices,
                                                      which make them fast operating (for arcing time see, Table 19.1),
                Arcing with contrate or slotted cup contact
                                                      it is possible to interrupt, such high-frequency  TRVs promptly.
                                                      19.6.1 Influence of frequency on the system
                                                      An a.c. current waveform passes through a natural zero
                                                      every one half  of  a cycle.  This is a highly  redeeming
                                                      factor  in  an  a.c.  system.  It  helps  to  extinguish  an  arc
                                                      promptly,  which  is  not  so in  a d.c.  system. A  higher
                                                      power  frequency  than  rated  would  in  fact  support the
                                                      extinction of an arc, irrespective of its other magnetizing
                                                      effects, while a lower power frequency than rated will
                                                      delay and add to the complications of extinguishing an
                                                      arc. At surge frequencies the situation becomes different,
                                                      as  the  zeros  occur  so frequently  that  the  contacts  are
        (a) Slotted cup type contacts of a 7.2 kV, 25 kA vacuum interrupter
              (Axial magnetic field type) (Courtesy: Siemens)   p


                                                                    ill1
                                                                    Ill1
                                                         TRV = 2.5  pu.  1
                                                                         Contacts break and
                                                                         arc extinguishes here


                                                           *
                 (b) Arcing with spiral petal contact
                  (Transverse magnetic field type)
       Figure 19.26  Magnetic arc control to increase the contact   I I  I I
       area of the arcing contacts  in a VCB                       I  I             Voltage wave --e
                                                                   I  I
       may interrupt before a natural current zero and cause a
       near  peak  system  voltage  across the  parting  contacts.   I  .  I  .  0.02 part of one half
       Figure  17.11(d) has been  redrawn  in Figure  19.27 for    I   I   cycle of the current wave
       more  clarity.  Under  the  cumulative  influence  of  the   I   (enlarged for clarity)
       reflected wave and the equipment’s back e.m.f., it may
       attain  a  value  of  high  TRV,  capable  of  breaking  the
       dielectric  strength  across  the  parting  contacts  of  the
       interrupting device. It may cause yet higher TRVs, until
       at least the immediate first natural current zero of the                     Current wave-
       interrupting  current.  See TRV  at  current  zero  (Figure
        19.27). Thus it would endanger the terminal equipment   at the immediate
       and the interconnecting cable. Such surge voltages (TRVs)   current zero ‘a’
       have increased  to 2.5-3  p.u.  in normal  operation.  It is
       possible that the arc does not extinguish at the first current   * Parting contacts are subject to this voltage which they are not
                                                       able to withstand and cause an arc raising the TRV up to 2.5 pu
       zero, point ‘a’ on the current wave. If a sufficiently high
       dielectric strength between the contacts is not attained,   Figure 19.27  Approximate  representation of  assumed voltage
       even by the next natural current zero (point ‘b’) by virtue   and current waveforms illustrating a current-chopping effect and
       of an extremely low contact gap or an inadequate insulation   its attenuation while  interrupting a circuit having 0.3 p.f.
   677   678   679   680   681   682   683   684   685   686   687