Page 699 - Industrial Power Engineering and Applications Handbook
P. 699

Temporary overvoltages and system grounding  201659
         20.1  Theory of overvoltages


         A three-phase balanced system has all the three phasors
         of voltage and current 120" apart. as illustrated in Figure
         20. I (a) for a conventional anti-clockwise rotation. These
         phasors  are  known  as  positive  sequence  components.
         During a fault. this balance is disturbed and the system
         becomes unbalanced  being  composed of  two balanced
         components, one positive and the other negative sequence
         (Figures 20.l(a) and (b)). For a description of the efiects
         of these components, refer to (Section 12.2(v)). During
         a  ground  fault,  zero  phase  sequence components  also
         appear, which are single phasor components and combine
         three equal phasors in phase,   hown in Figure 20. I (c).
         This is the residual voltage, Vg, that appears across the
         ground circuit,  i.e. between  the neutral and the ground
         as illustrated in Figure 20.12. This voltage is responsible
         for a fault current, I,  . Is will flow through the grounded
         neutral when it is a three-phase four-wire neutral grounded   Figure 20.2  An  ungrounded or isolated neutral system
                                                        (circuit completing through the ground leakage capacitances)
         system, as shown in Figure 20.12. It will also flow through
         a thrce-phase three-wire artificially grounded system when
         it  is $rounded  through a neutral  grounding transformer
         (Section 20.9.1 ) as illustrated in Figures 20.17 and 20.18.
         In a three-phase three-wire system, which has neither its
         own grounded neutral nor an artificially created grounded
         neutral. there will be no direct ground fault current. But
         charging currents through the ground leakage capacitances,
         particularly on an HT system, may still exist, as illustrated
         in Figures 20.2-20.3.
            These currents may  develop dangerous overvoltages
         across the  healthy  phases, under certain ground circuit
         impedance conditions, as discussed in Section 20.2. I( 1).
         It is thus possible to encounter a ground fault, even when
         the system is not grounded, the fault current finding its
         return path through the ground leakage capacitances. While
         an LT system. in view of a far too low ground voltage,  V,
         (equal to line voltage, Section 20.2.1( I)),  as compared
         to high ground capacitive leakage reactance. Xcg. would
         cause a near open circuit (V,/X,,  being too meagre) and
         stay immune. leaving the grounded conductor floating at
         v,  = v,                                       Figure 20.3  Case of  ground fault within the load





                                               v
                                                  v
                                             v
           B                                -__
                                            45436
          vlt                       -2% 1 I 1           N
            )  L  V  R     v>/


           Y iV            YV
               (a)            (b)            (C)
           Positive sequence   Negative sequence   Zero sequence or
                                        residual quantities                    ',    =G
         v, =  v, = v, = v                                                  -t

         Figure 20.1  Phasor representation of  an unbalanced power   Figure 20.4  Case of  a ground fault on a power system on
         system on a ground fault                       the load side
   694   695   696   697   698   699   700   701   702   703   704