Page 703 - Industrial Power Engineering and Applications Handbook
P. 703

Temporary overvoltages and system grounding  20/663
           Such  a  situation  may  also  arise  in  electromagnetic   This is measured between phase to phase or phase
         equipment, which is subject to a varying system voltage   to neutral, depending upon  the availability of the
         during normal operation. One example is a residual voltage   neutral. The test current is kept at the rated  value
         transformer (RVT) (Section 15.4.3) which is required to   for the equipment or the system under test. For the
         detect an unbalance (zero sequence) or a ground fault in   system shown in Figure 20.9(a).
         the  primary  circuit  and  may  reach  early  saturation. A
         similar situation is also possible in a measuring CT and   z, =-   VI
         even  a protection CT, as both may saturate at a certain   v'3 ' I,
         level of fault current in the primary. The same situation   22 = negative  sequence impedance.
         would arise in a CVT (Chapter  15). Such devices (CTs   This  is  the  same  as  above,  but  now  a  negative
         and CVTs) are generally grounded as a safety requirement,   sequence voltage is applied (by interchanging one
         and  may  give  rise  to  such  a  situation  during  normal   of the phases of the source of supply)
         operation, even  in a healthy system.          Zo = zero phase sequence or residual impedance. This
                                                            is measured between the three-phase terminals of
                                                            a  star winding  shorted  together  and  the  neutral
         20.3  The necessity for grounding an               (Figure 20.9(b)) and is calculated by
               electrical system

         An ungrounded system, in the event of a ground fault, is
         subject to an overvoltage, as noted in Section 20.2.1. It   where  - V  = test voltage and
         is prone to cause yet higher voltages in the healthy phases   43
         when its ground circuit becomes inductive, as discussed   I  = test  current, to  be  around  the  current-
         above.  Thc  ovcrvoltage  may  damage  the  supporting   carrying capacity of the neutral.
         insulators and the terminal equipment. Should a system
         be left ungrounded? This aspect must be viewed with the   Also  Zo = 3%  + 3%
         abohe  phenomena  in  mind.  It  may  also  cause  arcing   where Ro = zero phase  sequence or residual resistance,
         grounds and prove fatal  to a human body  coming into   and
         contact  with  the  faulty  equipment or  the  conductor.   X, = zero phase sequence or residual reactance
         Assuming that a total power system, from its generating   Zg = total impedance through the ground circuit
         station  to  the  far  end  LT  distribution  network  (Figure   Ig = ground fault current, zero sequence current
         13.21)  is  left  ungrounded  and  a  ground  fault  occurs   or residual current through the ground circuit
         somewhere on the LT side, the fault current through the   Vg = ground potential,  which  is  the  same as the
         human body will find a return path through the grounding   zero sequence voltage or residual voltage. In
         capacitances, no matter how feeble it may be. This current   a  ground  fault, it  would  remain  at  v;/&
         may be dangerous to a human for which even 10 mA is     unlike at Vt in an ungrounded system (Section
         fatal. as discussed in Section 21.2.1.                  20.2).
           Generally,  neutral  grounding  should  be  adopted  in
         principle  to  avoid  generation  of  overvoltages  and  to   The residual voltage may also be measured by a residual
         eliminate the  phenomenon  of  arcing  grounds.  Even  a   voltage transformer (RVT) (Figure 20. IO). Refer to Section
         solidly  grounded  system,  with  a  very  low  resistive   15.4.1 for more details.
         reactance, can avoid such overvoltages as the fault current
         on  a  ground fault will  find its  return path  through  the   Supply source
         rather than through the ground capacitances, which have  4
         shortest solid ground conductor, having a low resistance,
         a relatively much higher capacitive reactance. (See Figure
         20.12.)
           Below  we  briefly  discuss the critcria  and theory  of
         selecting a grounding system to achieve a desired level
         of  fault  current  to  suit  a  predetermined  ground  fault
         protection scheme, i.e. type of grounding and grounding
         impedance to suit the system voltage, type of installation,
         and location of installation.


         20.4  Analysis of a grounded system

         Consider  Figure  20.12  again,  when  the  neutral  N  is                     I
         solidly grounded. Also refer to Figure 20.1.  If   (a) To  measure positive   (b) To  measure zero
                                                          sequence impedance       sequence impedance
          V, = line voltage
          2, = positive sequence impedance                    Figure 20.9  Measuring system impedances
   698   699   700   701   702   703   704   705   706   707   708