Page 707 - Industrial Power Engineering and Applications Handbook
P. 707

Temporary overvoltages and system grounding 20/667
       To  achieve  the  desired  conditions  of  grounding, the   0
       following are the generally adopted grounding practices.
                                                          7
       20.6.1  An ungrounded or isolated neutral system

       When the system is totally isolated from the ground circuit,   6
       except through indicating, measuring or protective devices,
       which  are  normally  grounded  and  possess  a  high
       impedance to ground, the ground fault factor    5 1:



                                                       uo  3
       This may become higher,  depending upon the circuit's
       conditions  (for  example,  the  ferro-resonance  effect,
       Section 20.2.1.2).                                 2
       20.6.2  A grounded neutral system                  1
       When the system is grounded through its neutral, either   0
       solidly through a resistance or through an arc suppression   1  2  3 X,,/Xl -   6    7   %
                                                                                  5
                                                                              4
       coil  (inductor), it becomes  a grounded  neutral  system.
       This  type  of  system  grounding  may  be  classified  as
       follows:                                         R,, = Zero sequence resistance
                                                        X,,  = Zero sequence reactance
                                                        Xl  = Positive sequence reactance
         Effectively grounded
         Non-effectively grounded and                  Figure 20.16  Relationship between RdX1 and XdX, to determine
         Resonant  grounded systems.                   the values of ground fault factor kg based on IEC
       Effectively grounded system
                                                       20.7  Magnitude of temporary
       This is to achieve a higher level of fault current to obtain   ove rvo I t ag es
       a quicker tripping on fault. It is obtained when the system
       has a ground fault factor not exceeding 1.4 ( Vg I O.SV,),
       as noted above. A solidly grounded system will provide   At a particular location this can be obtained by multiplying
       effective grounding. This system will reduce the transient   the peak system phase to ground voltage by the ground
       oscillations  and  allow  a  current  sufficient  to  select  a   fault factor at that location. For example, for a 6.6 kV
       ground fault protection.  It is normally  applicable to an   nominal  voltage  system,  having  an  isolated  neutral
       LT  system.                                     (ungrounded  system),  the  maximum  temporary  over-
                                                       voltage during a ground fault may rise to
       Non-effectively grounded system                 Vph(peak) x GFF
       An impedance grounded system will fall into this category.          6.6
                                                                           a
       The GFF may now exceed  1.4 (Vg > 0.8Ve).       where  Vph (peak) = fi x - kV = 1 p.u.

       Resonant grounded system                        and  GFF =   for an ungrounded  system
       When the system is grounded through an arc suppression   :.  Temporary overvoltage = 1 pa. x 8
       coil  (reactor)  so that  during  a  single  phase  to ground       = 4p.u.
       fault,  the  power  frequency  inductive  current  passing
       through the inductor coil would almost offset the power
       frequency  leakage capacitive component of the ground
       fault current. However, such a situation is not allowed to   20.8  Insulation coordination
       persist for more than  8 hours in any 24 hours or for a
       total of  125 hours during a year. If  it is more, a higher   For non-effectively grounded systems, having a GFF of
       level  of  insulation  (BIL)  will  become  necessary.  The   more than  1.4, a higher level of insulation (BIL) will be
       ground fault factor in this case may also exceed  1.4.   essential for all equipment being used on the system to
          When the system parameters Ro, Xo and XI are known,   withstand a higher level of a one-minute power frequency
       the value of GFF may be determined more accurately by   voltage test as well as an impulse voltage withstand test
       the use of Figure 20.16, which has been established for   if  such levels (Lists I, I1 and  111)  are prescribed  in the
       different grounding conditions, Le. for different  values   relevant standards. If not, then it may be assumed, that
       of Ro. Xo and XI.                               the  prescribed  test  values  take  account  of  such  an
   702   703   704   705   706   707   708   709   710   711   712