Page 711 - Industrial Power Engineering and Applications Handbook
P. 711

Temporary overvoltages and system grounding  20/671
                                                        and Table 13.6). As  a result, the ground fault current in
                                                        a generator circuit is greater than its three-phase symme-
                                                        trical fault current. This current rises further when all of
                                                        them are individually grounded and more than one unit
            os  z,,      V,?     n              (20.6)   are running in parallel at a time. It is worth  mentioning
                  =
                     11, 1000. kVA                      that when two or more generators are running in parallel
            From  this  equation  one can  determine  the  required   and all of them are grounded, they form a closed circuit
            calue  of  neutral  circuit  impedance  for  a  particular   to cause circulating currents. This may occur even in a
            level of ground fault current. The external impedance   healthy system due to unbalance, not because of single-
            will be Z,,  less the ground impedance. In HT systems   phase loads but unequal generator phase currents due to
            one can also determine the  likely value of  a ground   eddy currents. These are important aspects and must be
            inductor coil  to  achieve a near-resonance condition,   considered while deciding on the grounding method of a
            to eliminate the arcing grounds, on the one hand, and   solidly  grounded  generator.  Consider  Figure  20.20,
            facilitate  a  strike-free  extinction  of  an  arc  by  the   illustrating four identical generators operating in parallel.
            interrupting device, on the other.          Each has the following reactances:
                                                        positive  phase  sequence  instant  p.u.  (sub-transient)
         Example 20.1                                   reactance =  XC
         For a 1600 kVA, 11/0.415 kV transformer,  considering the LT
         side                                           negative  phase sequence p.u. reactance  = x2
          z,  (0 415)'  x  1000'                        zero phase sequence p.u. reactance   = xo
            =
              nx1000x1600
                                                        :.  Total p.u. reactance of the ground circuit
         For an industrial power distribution network, if the setting of
         the protection relay is considered to be 20% of  I, then
                                                        s = x;'  + X? + .Xg
          z-  (0 415)'~ 10002  ~I                       For the sake of illustration, consider the values of these
           ' - 0 2 x 1000 x  1600                       reactances as in Example  13.4:
            = 0 54 CL                                   xy = 11.7%
         The natural zero phase sequence inductive reactance of the   x2 = 8.89
         grounded neutral may be considered  to be too small compared
         to this and ignored for ease of calculations Thus the resistance   = 4.0%
         Ro of  the grounded neutral circuit may be considered as its
         impedance, i e                                 The instant (sub-transient) fault current, lssc, through a
                                                        generator in a symmetrical three-phase system, irrespective
              0 415 x 1000
          I,  =                                         of the condition of neutral  as defined in Table 13.9 will
               L3 x 0 54                                be
            ==  444 Amps                                                       V
                                                        list (3-$  fault peak value) =
         The  impedance  calculated  thus  will  form  the  basis  of          21 <I
         determining the adequacy of the grounding stations provided.   where v = p.u. voltage
         Probably, for such a low value of grounded neutral impedance
         the grounding stations  may have to be more elaborate and   for x;'  = 11.7%, I,,,  = - or 8.55 v
         greater  in numbers (arranged in parallel). This is to ensure    0.1 17
         that at  no stage will the  impedance of  the system  increase
         beyond 0.54 R  (inclusive of  the  impedance of  the ground).
         Otherwise it will render the protective scheme ineffective and
         allow the ground fault to persist.                 G1        G2                  G4
            The above is the case for an LT system. For an HT system,
         similar calculations may be carried out to determine the ground
         neutral impedance. Now it will be much higher than the above
         due to a high  Vg to limit the fault current and thus also the
         ground potential difference to below a dangerous level at any
         point  on  the  ground  circuit.  The  impedance  of  the  ground
         circuit in such cases may be increased through a resistance
         or an inductor coil.                             Neutral* $     * $        *)

         20.10.1  Grounding of generators                   bus                               *$
         Solid grounding
                                                                                            -G
         Generators  that  are  solidly  grounded  have  a  different   Impedance of each machine Z,, Z,,  Z,
         grounding  practice from others due to their zero phase   * Neutral grounding switches  (only one to be 'ON' at a time)
         sequence reactance. which is much less than its positive
         or negative phase sequence reactances (Section 13.4.1(5))   Figure 20.20  Recommended neutral grounding of generators
   706   707   708   709   710   711   712   713   714   715   716