Page 709 - Industrial Power Engineering and Applications Handbook
P. 709

Temporary overvoltages and system grounding  20/669
            If  the  above  are  not  taken  into account  the  devices   Note
         and  components  used  on  the  system  may  have  to  be   The magnetic  core  is designed  so that  it  will  not  jaturate  during
         selected or braced for a higher system voltage, say, up to   normal operation  to avoid  a ferro-resonance  condition.  The knee
         twice the  rated  voltage or even more. The overvoltage   point voltage is kept at about  I .3 times the system  line voltage.
         condition  may  almost  be  the  same  as for  ungrounded
         capacitor switching (Section 23.5.1 (ii)).
                                                        Residual voltage transformer (star/open delta
         Neutral grounding transformers                 trans former)
         The artificial neutral point on the delta side can be created   This is not a method of providing an artificial neutral. as
         by  providing an interconnected star neutral, also known   in the previous case, but to detect an unbalance or residual
         as a iig-zag transformer. It can also be provided through   voltage (zero sequence voltage) in  a three-phase three-
         a star-delta  transformer. Both arrangements are illustrated   wire or a three-phase four-wire ungrounded system. The
         in Figures 20.17 and 20.18 respectively. Such transformers   residual or zero sequence voltage that may appear across
         are of a standard core type, with only a single winding   the open delta will be the reflection of an unbalance or a
         on each transformer limb, split into two halves as shown.   ground fault in the system (Figure 20.10). Also refer to
         The  total  winding  arrangement  is  like  a  1:1  auto-   Section  15.4. I  for more details.
         transtormer,  with  the  provision  of  altering  the  ground
         impedance, similar to that in a normal ground circuit, as
         discussed above. The additional resistance or impedance,   20.1 0  Important parameters for
         as required in the ground circuit, may be provided either   selecting a ground fault
         by  inserting it between the neutral point and the ground
         or  in  the  three  individual  phases  as  shown  in  Figures   protection scheme
         20.17 and 20.18.
            The rating of the auxiliary transformer can be short-   1  Single-phase loads or unevenly distributed loads on a
         time. sufficient to feed the fault current and its own no-   balanced three-phase  system do not  lead  to a faulty
         load  losses fot, say, 30 seconds or so, according to the   condition as a result of unbalanced currents. The single-
         maximum  tripping time of the  protective  scheme. The   phase load currents will always have the return  path
         normal rating of such transformers is generally between   through the neutral and not the ground. The current
         5  and  100 kVA, sufficient to carry the full ground fault   through the ground circuit will flow only when there
         current. The winding is designed for line-to-line system   is  a ground  fault  and the  circuit  completes  through
         voltage.                                         the ground loop. Refer to Figures 20.19(a) and (b).




            Delta connected                     Delta connected
              transformer                         transformer
               windings                            windinas
























                    (a) Current-limiting  resistor in  neutral   (bj Current-limiting  resistors in  line   (c) Phasor  representation  of
                                                                                  the grounding transformer
                               Figure 20.17  36 interconnected star-neutral grounding transformer
   704   705   706   707   708   709   710   711   712   713   714