Page 705 - Industrial Power Engineering and Applications Handbook
P. 705

Temporary overvoltages and system grounding  20/665
                                                          With such a system the possibility  of an arcing ground
                                                        is almost eliminated and it is now possible even to allow
                                                        the  ground  fault  condition  to  prevail  until  it  can  be
                                                        conveniently repaired. Now  it  will  cause no harm  to  a
                                                        human  operator,  supporting  insulators  or  the  terminal
                                                        equipment. On long-distance transmission or distribution
                                                        networks  such  a  situation  may  rather  be  desirable  to
                                                        prevent the system from tripping instantly until  at least
                                                        the off-peak periods or until the supply is restored through
                                                        an alternative source. The  process  of  finding  the fault
                                                        and its repair may be allowed to take a little  longer.
                                                          A neutral grounding reactor (NGR) is also desirable
                                                        to achieve auto-reclosing of a faulty phase during a one-
                                                        pole opening as a result of a fault of a transient nature on
                                                        this phase (Section 17.4.1). The reactance grounding will
                                                        limit  the  high  unbalanced  capacitive  currents  through
                 Z,  = Tapped reactor or arc suppression coil
                                                        the healthy phases to ground and prevent an unbalance
            Figure 20.13  An impedance grounding  neutral system   and  so  also  an  unwanted  trip  as  illustrated  in  Figure
                                                        20.14.  Referring  to  Figure  20.14,  a  ground  fault  of  a
                                                        transient  nature  on  phase  B  would  cause  the  two  line
         If  I,"  = fault current through the healthy phases due to   breakers b and h'  to trip and result in heavy ground fault
                ground capacitive reactance Xce, then the current   current  through  the capacitive coupling  of  the  healthy
                through the ground capacitive reactances
              = c+                                     phases.  The  NGR  would  neutralize  such  currents  and
                                                        phases, eventually also tripping the breakers ofthe healthy
                                                       prevent  an  unwanted  trip, achieve the  desired  auto re-
              =  \3.1:                                 closing and improve system stability. For such a situation
                                                        to arise it is tuned to a zero p.f. to achieve a near-resonant
         And  the total  ground fault current           condition so that the fault current, Ig, is almost zero, and
                                                       the capacitive current is substantially offset by the power
                                                       frequency inductor current, i.e.
           The value of I,  can thus be  varied  in magnitude and
         phase  displacement  to  suit  a  particular  location  of
         installation or protective scheme by introducing suitable
         R and X,~ into the neutral circuit. When the impedance is   where the total  ground capacitive reactance
         inductive.  the fmlt current  1; will also be inductivc and
         will  offset  the  ground capacitive current  I:.  In  such a
         grounding, the main purpose is to offset the fault current
         as much  as possible  to  immunize  the  system from  the
         haurds of an arcing ground. This is achieved by providing   If  L = inductor coil  inductance in henry
         an  inductor coil. also known as an arc suppression coil,   C,,=  ground capacitance per phase in  farad  and
         of a suitable value  in the neutral  circuit.     f = system frequency in Hz

         20.5  Arc suppression coil or ground           Coupling (leakage)
               fault neutralizer                          capacitances          Transmission line
                                                                                   ,
         This  is  also known  as  a  Petersen  coil,  named  after  its
         inventor. With an inductive reactance, X,,  in the ground        \-               i
         circuit  the  ground  fault  current  can  be  substantially
         neutralized  by  tuning  the  inductor  correctly. A  small                            .R
         residual  ground current however, will  still flow through                   t  t  t\
         the ground circuit as a result of its own resistance, insulator
         leakage and corona effect. In all likelihood, it would be   ' P
                                                                                      44
                                                                                  I
         sufficient  to  operate  the  protective  scheme.  Since  the      I   'I  grounding Neutra:{ 1
         fault current is now  nearly in phase with the voltage of
         the healthy phases, it will prevent the interrupting device   grounding NeutralF
         from causing a restrike while interrupting the fault (Section
         17.7.2(iii)). Such  an  arrangement  is  more  appropriate   reactor (NGR)   reactor (NGR)
         for  systems  that  are  above  15 kV  and  are  subject  to
         frequent  ground  faults,  for  example  an  overhead
         transmission  line or a long distribution system.     Figure 20.14  A ground fault  neutralizer
   700   701   702   703   704   705   706   707   708   709   710