Page 710 - Industrial Power Engineering and Applications Handbook
P. 710

201670  Industrial Power Engineering and Applications Handbook

        Delta connected                     Delta connected
          transformer                        transformer
           windings   IQ                      windings   1,

                                                                                       Neutral may be
                                                                                      resistor grounded
                                                                                      or solidly grounded



















                   (a) Current-limiting  resistor in neutral   (b) Current-limiting  resistors in line   (c)  Phasor representation of
                                                                                 the grounding transformer
                                 Figure 20.18  34 Staridelta neutral grounding transformer
                                                       2  The magnitude of the ground fault current is a matter
                                                         of  system  design  and will  largely  depend  upon  the
                                                         system  voltage  and  the  ground  loop  impedance,  as
                                                         discussed above. The theory of grounding protection,
                                                         however.  is  different for an  LT  and  an  HT  system.
                                                         While  an LT  system  will  require  a reasonably  high
                                                         ground  fault  current  and thus  a  low  ground circuit
                                                         impedance to detect the fault promptly, an HT system
                                                         must have as low a ground leakage current as possible
                                                         to avoid  a dangerous potential gradient at any point
                                                         on the ground loop and the  ground  (step and touch
                                                          voltages, Section 22.9) and to eliminate the danger to
         G                                               a human coming into contact with it and also to prevent
                                                         arcing grounds. HT systems as standard practice are
                        (a) Healthy system               therefore  designed  to  have  a  high  ground  circuit
                                                          impedance.
                                                       3  The required ground  impedance may be determined
                                                          on the following lines, if
                                                          kVA  = rated  capacity  of  the  supply  source, which
                                                               can be a generator or a transformer
                                                            Vi  = system rated  line voltage in volts
                                                            I,. = system rated full-load line current in amperes
                                                           Zg = impedance of the grounded neutral circuit in
                                                                ohms
                                                            I,  = required  level  of  the ground  fault current  in
                                                                amperes
                                                          Then

                                                               =       R
                                                             z, ~   "(
                                                                 .\15 . I,
                         (b) Faulty system                and  I,  =   1000 ' kVa   Amp
                                                                  47. v,
                                                          IF is generally defined in terms of Ir, such as 1040%
         Figure 20.19  In a healthy system the unbalanced current
         (other than a ground fault or  phase to phase and ground fault)   or 20-80% of Ir, depending upon the protection scheme.
        will flow through the neutral and not the ground   If I,  is, say, n  in units  of I, then
   705   706   707   708   709   710   711   712   713   714   715