Page 713 - Industrial Power Engineering and Applications Handbook
P. 713

Temporary overvoltages and system grounding 201673
       will become as follows when all the four generators are   recommended  to  limit  the  TRV  by  inserting  a  small
       grounded and are operating in parallel and one of them   resistance into the grounding circuit to make the ground
       develops a ground fault:                       fault current (Ig) somewhat resistive than capacitive due
                                                      to  capacitive  coupling  between  the  generator  and  the
                   3v
        I"=-     - - -x4                              associated  equipment  and  the  ground  as illustrated  in
         g
             xz+  x2 + xo + 3r                        Figure  20.21.  To  achieve  this,  the  ground  fault  loss
                        4 x 3v                        represented by   R  (Igr being the active current and R
           -
           -                                          the ground resistance) should be higher than the electrostatic
             J(O.117 + 0.088 + 0.04) + 3 x 0.09       loss to ground, as explained in Example 20.2.
           -   4 x 3v                                   Since a reactor  can  only offset or over-compensate
           -
             0.27 + 50.245                            the capacitive kVA, it will not yield the same result as a
           --                                         resistance.  Resistance  grounding  is therefore  preferred
             4 x 3v
           -
             0.365                                    to reactance grounding. The GFF, however, will now be
       or  32.88~                                     higher and may rise to  fi times. The phase to neutral
                                                      voltage in the healthy phases may rise to the line voltage
       This  is  less  than  the  corresponding  symmetrical  fault   during a ground fault, as in an isolated neutral system.
       current  of  34.2~ and  incidentally  equal to the  ground   Machine  insulation  and  all  equipment  and  devices
       fault current  when  only one machine  is grounded  at a   associated with the machine must take care of this. The
       time. By  this  method,  the ground  fault current  can be   low-resistance  grounding  may  be  achieved  through  a
       controlled to any  desired  level. We  have considered  a   distribution  transformer,  with  a  low  resistance  on  the
       resistance with a view to improving the p.f.  of the fault   secondary side, as shown in Figure 20.21.
       current and thus, making it easier to interrupt.
                                                      Example 20.2
       Level of ground fault current for large generators   To determine the grounding parameters, consider a generator
                                                      rated for 200 MW, 15 kV and the ground fault current limited
       Manufacturers of large generators, 200 MW and above,   to  15 A.  Considering GFF as  6, the voltage ratio of  the
       recommend the ground fault current, Ig to be limited in   grounding transformer with a 220 V secondary will be
       the range of 5-15  A and a fault clearing time of the order
       of  5-30  seconds  to  protect  the  machine  and  avoid   15, & kV:220 V
       overheating  of  the  grounded  steel  frame.  It  is  also   6
                                                      or 15 kV:220 V
               To  grid
                                                      Consider safe /gr  as 10 A.

                                                      1. Electrostatic kVA
                                                      Consider the following ground and other leakage capacitances
        Generator
       transformer                                    for the sake of reference:
                                                      Generator to ground = 0.5 pF
                                                      Generator bus duct to ground = 0.15 pF
                                                      Low-voltage winding of GT to ground = 0.007 pF
                                                      Surge capacitance = 0.2 pF
                                                      :.  Total coupling capacitance = 0.857 pF
                                                      and coupling reactance
                                                      x-           1         (for a 50 Hz system)
                                                        cg  - 2n x 50 x 0.857 x lo4
                                                         = 3.72 x 103 n
                                                                              15 000
                                                      and coupling current  IC,  =
                                                                          &i 3.72 x io3
                                                                             x
                                                                        = 2.33 Nper phase
                                                                   3 . ICc  = 6.99 A for three phases
                                                      and electrostatic kVA
                                         I
                                                                x
           I___________,________---l                       = 15 6.99
                                                             d3
                                      3.1,
                                                           = 60.53 kVAr
         I,  - Ground and other leakage currents per phase.
         Is, - Ground fault current through the generator
         R - Secondary grounding resistance           2. Ground fault loss
                                                      Secondary current on fault
       Figure 20.21  Grounding method and flow of ground fault
       current in a generator on a ground fault (Example 20.2)     v, *  I,  = v, . /2
   708   709   710   711   712   713   714   715   716   717   718