Page 706 - Industrial Power Engineering and Applications Handbook
P. 706

20/666  Industrial Power Engineering and Applications  Handbook
         then                                          appropriate  ground  fault  protective  scheme as well as
                                                       the insulation level for that system. It is defined as the
                                                       ratio of the highest voltage to ground, Vg (r.m.s.), of the
                                                       healthy  phase  or  phases  during  a  ground  fault  to  the
                                                       corresponding  power  frequency  phase  voltage  V, /&
         or  L       1     henry               (20.4)   when the system was healthy.  Refer to Figure 20.15.
                       .
               3(2~f)~ Cg
                                                                                  "E
                                                        :.  Ground fault factor (GFF)  = -  (20.5)
         It  is  likely  that  for  reasons  of  system  disturbances,           v, 143
         frequency fluctuations and switching of  a few sections
         of the system, both X, and Xcg may vary in actual operation   which is usually more than  1.
         and upsct the resonance condition, leading to transient   It is also established that in an effectively grounded
         overvoltages. To  overcome this, the  inductor  coil  may   system the voltage to ground, Vg, of the healthy phases
         be made variable  (the setting of  which may be altered   does not exceed 80% of the line-to-line voltage  V, and
         automatically)  through  a  motor-driven  tap  changer  to   consequently  the GFF does not  exceed 0.8 x  4, i.e.
         achieve the tuning again. If the ground fault persists the   1.4. The system may be considered as effectively grounded
         inductor coil may be rated continuously rather than for a   when
         short time and for the full fault current that the coil may
         have to carry.
                                                          x+
           To  overcome the  generation  of  overvoltages  across   o= between 0 and 3, and
         the inductor coil (Section 20.2.1(2)) its inductance, L, is   R
                                                             =
         generally selected high, so that the resonance condition   2 between 0 and 1
         with the ground capacitors,  C,,  occurs near the natural   X+
         frequency of  the system (SO or 60 HL) and the voltage
         developed  across  the  inductor  coil,  Vi, may  oscillate   where
         only  at  around  Vel&.  Generally,  the  Petersen  coil   Xo = zero sequence reactance
         neutralizer is a high-reactance grounding and is also termed   Ro = zero sequence resistance
         resonant grounding, free from overvoltages and restrikes.   X,  = positive sequence reactance
         Equating the voltages developed across the Petersen coil

                                                                                       R

         The voltage developed would thus oscillate around the                         Y
         normal voltage and fall in phase with the fault current to
         achieve a near-strike-free interruption of the interrupting
         device on a ground fault.                                                     6

                                                                          v, Id 3
         Note                                                 --1
         1  Aa  in  IEC  60071-1,Za  higher  insulation  level  (BIL)  w~ll be
            necessary  for all insulators and terminal  equipment when  the
            ground fault persists for more than  8 hours per 24 hours  or a   rG
            total of  more than  125 hours during a year.
         2   Because  of  likely  de-tuning and  generation  of overvoltages,   (a) Healthy system
            this system is seldom in practice.
            Sometimes  such  a  situation  may  arise  on  its  own,
         even on a normally  grounded system, not  intendcd for
         ground  current  neutralizing.  It  can  happen  when  an
         overhead line snaps due to a storm, winds or any other
         factor and falls on trees, hedges  or dry metalled roads
         and remains energized in the absence of a proper return
         path and cause a low leakage current, insufficient to trip
         the protective circuit. This is a situation not really desirable
         on a normally  grounded  system, as  it  may  lead  to  an
         ungrounded system and may develop overvoltages.         G     =G
                                                                       (b) Faulty system
         20.6  Ground fault factor (GFF)                R &  Y - Healthy phases
                                                           6 - Faulty phase
                                                          V, - (rms) value of ground voltage measured on fault
         This is an important indicator that shows the grounding
         condition of a system and helps to determine the most   Figure 20.15  Determining the ground fault factor
   701   702   703   704   705   706   707   708   709   710   711