Page 773 - Industrial Power Engineering and Applications Handbook
P. 773

23/730  Industrial Power Engineering and Applications Handbook









                                                        II I
                              Voltaoe wave   ’P‘







                                                                            Switch recovery
                                                                            3rd interruption

                                                                        i
                                                                        c“
                                          I     cycle    I    cycle
                           (90” leading)
                               \          I              I


                                                         2nd current     3rd current
                                     zero                  zero            zero
                                         1st            1 st          2nd
                                       interruption    restrike      restrike
                                            Time --m
            Figure 23.5  Build-up of  capacitive voltage  (TRV) on restrike during contact  interruption in a grounded star HT capacitor unit



          the interruption of a grounded capacitor unit seldom exceed   0.5 p.u. + 0.866 p.u. or  1.366 p.u. (max.)
          2.6 p.u.  as  a  result  of  self-attenuation  and  high-speed
          modern interrupters.                           where 0.5 p.u. = trapped charge and
                                                                   217
          (ii) Ungrounded capacitor units (both star- and   0.866 p.u. = 7 p.u.  is  the  excitation  due to  lumped
          delta-connected units)                                    I
                                                         capacitances of the unswitched phases.
          Consider the arrangements shown in Figures 23.3(b) and   The parting contacts will therefore now be subjected
          (c). Now the opening of the switch in one phase will not   to a TRV of 3 p.u. at the first interruption. If the contacts
          isolate the capacitor in that phase from the system, as in   fail to interrupt at point a’, the arc will strike again, and
          the grounded system as a result of  a feedback through   by the next current zero (point b’  on the current wave),
          the lumped (leakage) capacitances of the other two phases   when they will try to interrupt again, will be subjected to
          (Section 20.1 and Figure 20.2). Assume the initiation of   a TRV of 4 p.u. Refer to point bb”on the voltage wave,
          interruption in one of the phases at a current zero. Refer   assuming that the capacitor unit is still retaining its charge.
          to point  a’  on  the  current  wave  (Figure 23.6(a)).  The   The cycle of an arc restrike will be repeated at the next
          parting contacts will now be subjected to an additional   current zero c’,  at 5 P.u.,  point cc”  on the voltage wave.
          voltage equal to the system voltage of  1 P.u., because of   The process  will  continue  until  the circuit  will  finally
          the other two phases, which would also be conducting,   interrupt by virtue of the interrupter’s ability to interrupt
          besides  2 p.u. at point  ‘a’ as discussed in the previous   or attenuation of the TRV, whichever occurs first. Field
          case. The other two phases which  are now  conducting   experiments  have  revealed  that  overvoltages  due  to
          will  each retain  a  charge  of  0.5 p.u.  at  every  voltage   repeated restrikes during the interruption of an ungrounded
          peak in the first phase, as illustrated in Figure 23.6(b).   capacitor unit,  connected in  star or delta, will  seldom
          This  charge  will  be redistributed  in  the  first phase  as   exceed  3  p.u.  due  to  self-attenuation  and  high-speed
          soon as its contacts open. The unswitched phases, however,   modern interrupters. The system grounding has no effect
          will retain a charge of                        on such ungrounded capacitor units. The interruption of
   768   769   770   771   772   773   774   775   776   777   778