Page 867 - Industrial Power Engineering and Applications Handbook
P. 867

Table 25.2  Rating and selection of components for capacitor duty

 Type of   Reference   voltage class   Insulation  level   Current rating   Fault level   Any other requirement
 component   Standard   (M and time)

 1   2   3   4   5      6           I
 Isolator   LT  ~  IEC 60947-3   As per the   As in Tables   As for the   For LT isolators minimum duty AC23.
 HT - IEC 60129   voltage rating   13.2 and  14.3   main system.   (Table 12.5)
 of the capacitor   for Series I or   Minimum 150% of
 banks (Section   the rating of the
 23.12.1)   Table  14.1 for   capacitor banks.
 (average voltage)  Series I1 voltages   For systems prone
     to generating
 HRC fuses   LT  ~  IEC 60269   excessive
 HT - IEC 60282-1,   harmonics, and
 60549 and 60644   when the size of the
     reactor, if used,  is
 Circuit   LT - IEC 60947-4- I   not sufficient to   1  For LT  systems, it may be a switch and
 interrupter   (for contactors)   suppress these, ratings   a contactor, ACB or MCCB. When a
 HT ~  IEC 600.56   up to 200% are    contactor, they would be minimum AC3
 (for circuit breakers)   recommended.   or AC6b duty. (Table 12.5).
                                    2  For HT systems, refer to Table 19.1,
                                     for the selection of  interrupters for
                                      capacitor duty. The breaker should be
                                      chosen restrike free, as far as possible.

 Cables and   Refer to Table
 conductors   A16.1  in  Chapter 16
 ._                    __   ~
 Series reactor   IEC 60289   Refer to column 5   I  For smaller units, they   Refer to   1  For limiting inrush currents: Generally,
       are used to limit only   column 5   it is not required  for the LT  systems.
       the inrush currents            For larger banks, however, say, 500 kVAr
       during a parallel              and above, when they are installed
       operation and may be           close to the supply source, so that the
       rated for 0.2% of the          line reactance  up to the bank is too
       capacitors’ kVAr               small to limit the switching currents,
       rating. They must be           the use of reactor  would be advisable.
       connected on the
       neutral  side of  a star-    2  For suppressing harmonics:  since on an
       connected capacitor            LT system, the capacitor banks are
       bank. Also refer to            normally  small, there is generally  no
       the notes below  step 4        need to provide a reactance to suppress
       of Example  23.4.              the harmonics. It is, however, advisable
       The series reactor             to provide this for larger banks above
       may not be suitable to         500 kVAr to contain the overvoltages
       withstand  the system          on account of this, to save the other
       fault level, nor add           devices also operating on the same
       significantly, to the          system. For the likely magnitudes  of
       circuit impedance  to          harmonics on an LT  system, refer to
       diminish  its fault level.     Table 23.1.