Page 195 - Industrial Process Plant Construction Estimating and Man Hour Analysis
P. 195

Coal-fired power plant Chapter  8 171


                Install duct support steel
                Install inlet ductwork on the support steel including the louver dampers
                Install seal air system platform on duct support steel
                Set seal air fan and heater
                Support structure
                Sliding plates and cap plates



             8.36 Electrostatic precipitator estimate data

             8.36.1 Hoppers, casing/partition frames, support steel, diffusers,
             TEF’s & IRB’s sheet 1


             Description                                      MH         Unit
             Preassemble hoppers
             Place hopper cones and baffles                   1.80       0
             Place side wall sections                         1.50       0
              Weld side wall and hopper baffles               0.32       LF
              Clean out door                                  4.00       EA
             Preassemble casing and partition frames
              Place and fit side and partition frame sections  10.00     0
              Weld side frame and partition sections—3/8 square butt weld  0.75  LF
                                            00
              Bevel beams 1/2 thick   12 00                   2.50       Ea.
                         00
              Place and fit beams                             10.00      Ea.
              Full penetration field weld 1/2 double bevel    16.80      Ea.
                                   00
             Erect precipitator support steel
              Erect and bolt structural columns               40.00      Ea.
              Erect X—bracing                                 21.00      Ea.
              Bolt X—bracing                                  3.40       Ea.
             Preassemble diffusers                            240.00     Job
             Preassemble perforated plates
                                                      0
                                                  00
                                                 0
              Load, haul, offload inlet/outlet perforated plates 11 -3   5 -0 00  2.00  Ea.
              Place and fit perforated plate sections         4.00       Ea.
              Weld perforate plate sections                   0.35       LF
              Place and weld clips                            1.00       Ea.
             Preassemble TEFs and IRBs
              Load, haul, offload frames                      2.76       Ton
              Set top-end frames                              20.00      Ea.
              Set intermediate roof beams                     32.00      Ea.