Page 238 - Industrial Process Plant Construction Estimating and Man Hour Analysis
P. 238

214 Industrial Process Plant Construction Estimating and Man-Hour Analysis


            9.24 Air cooled condenser installation man hours
            9.24.1 Facility—solar power plant (10 cell ACC)


                                              Historical    Estimate  Actual
                                                            MH/      MH/
            Description                   BM    IW   PF     Module   Module
            Erect structural steel modules 1–6  0.0  0.0  0.0  0.0   263.1
            Fan duct support steel modules 1–6  0.0  0.0  0.0  0.0   4.0
            Preassemble stairways at grade and set  0.0  0.0  0.0  0.0  11.4
              and secure
            Preassemble external walkways at grade  0.0  0.0  0.0  0.0  18.6
            Upper structure A-frame steelwork  0.0  0.0  0.0  0.0    294.7
            Fan inlet cowl and fan screens  0.0  0.0  0.0   0.0      92.4
            Motor support bridge          0.0   0.0  0.0    0.0      85.6
            Erect and weld tube bundles   0.0   0.0  0.0    0.0      163.1
            Erect and weld condensate headers  0.0  0.0  0.0  0.0    203.9
            Erect and weld steam distribution  0.0  0.0  0.0  0.0    192.8
              manifolds
            Erect and weld IC equipment pipe  0.0  0.0  0.0  0.0     81.7
            Erect and weld IC street pipe  0.0  0.0  0.0    0.0      155.7
            Erection and sheeting of wind walls  0.0  0.0  0.0  0.0  173.0
            Erect and weld turbine exhaust duct  0.0  0.0  0.0  0.0  163.3
            Field assemble street steam duct  0.0  0.0  0.0  0.0     272.4
            Erect and weld out risers     0.0   0.0  0.0    0.0      107.9
            Set and assemble shop tanks   0.0   0.0  0.0    0.0      8.8
            Pumps                         0.0   0.0  0.0    0.0      120.0
            Install expansion joint at turbine  0.0  0.0  0.0  0.0   43.3
            Pneumatic testing             0.0   0.0  0.0    0.0      33.3
            Air cooled condenser installation  0  0  0      0.0      2489.0
                man-hours
            Actual number of streets   modules ¼  2  5  10
                number of cells
            MH/module   number of cells ¼  2489  10  24,890
                estimate man-hours
            Estimate number of streets   modules ¼  0  0  0
                number of cells
            MH/module   number of cells ¼  0    0    0
                estimate man-hours
   233   234   235   236   237   238   239   240   241   242   243