Page 64 - Industrial Process Plant Construction Estimating and Man Hour Analysis
P. 64

Process piping Chapter  2 35


             2.4.3  Welding—SOL, TOL, and WOL
             Facility—Diesel power plant

             Man-hours per SOL, TOL, and WOL
                                       Wall thickness in inches
              Pipe
                        00
                                   00
              size  0.375 or less 0.406 –0.500 00  0.562 –0.688 00  0.718 –0.938 00  1.031 –1.219 00
                                                                      00
                                               00
                                                          00
               0.5     1.60        2.00       3.80        4.80       5.80
              0.75     1.60        2.00       3.80        4.80       5.80
               1       1.60        2.00       3.80        4.80       5.80
               1.5     1.60        2.00       3.80        4.80       5.80
               2       1.60        2.00       3.80        4.80       5.80
               2.5     1.75        2.00       4.25        5.75       7.00
               3       2.10        2.10       2.40        6.90       6.90
               4       2.80        2.80       3.20        6.80       9.20
               6       4.20        4.20       4.80       10.20       13.80
               8       5.60        5.60       6.40       13.60       18.40
               10      7.00        7.00       8.00       17.00       23.00
               12      8.40        8.40       9.60       20.40       27.60
               14      9.80        9.80       11.20      23.80       32.20
               16      11.20      11.20       12.80      27.20       36.80
               18      12.60      12.60       14.40      30.60       41.40
               20      14.00      14.00       16.00      34.00       46.00
               24      16.80      16.80       19.20      40.80       55.20
             SOL, TOL, and WOL welds; two times BW (includes cut, prep, and fit up).
             Wall thickness of the pipe used for weld determines man-hours that will apply.
             PWHT butt welds greater than or equal to 0.750 .
                                          00
             Apply percentages for welding alloys and nonferrous welds.