Page 43 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 43
SHORT CIRCUIT TEST (referred to the high-voltage or primary side):
17.1 V
Z R jX 1.97
EQ EQ EQ
8.7 A
P 38.1 W
cos 1 SC cos 1 75.2
VI 17.1 V 8.7 A
SC SC
Z EQ R EQ jX EQ 1.97 75.2 0.503 j 1.905
R EQ 0.503
X EQ j 1.905
To convert the equivalent circuit to the secondary side, divide each series impedance by the square of the
turns ratio (a = 230/115 = 2). Note that the excitation branch elements are already on the secondary side.
The resulting equivalent circuit is shown below:
R EQ,S 0.126 X EQ,S j 0.476
R CS 3383 X MS 1099
,
,
(b) To find the required voltage regulation, we will use the equivalent circuit of the transformer referred
to the secondary side. The rated secondary current is
1000 VA
I . 8 70 A
S
115 V
We will now calculate the primary voltage referred to the secondary side and use the voltage regulation
equation for each power factor.
(1) 0.8 PF Lagging:
36 87 A
P V S V Z EQ S 115 0 V I j 0.126 0.476 8.7 .
P V 118.4 1.3 V
118.4-115
VR 100% 2.96%
115
(2) 1.0 PF:
8.7 0.0 A
P V S V Z EQ S 115 0 V I j 0.126 0.476
P V 116.2 2.04 V
37