Page 50 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 50
SOLUTION
(a) The transformer supplies a load of 80 MVA at 0.8 PF lagging. Therefore, the secondary line current
of the transformer is
I LS S 80,000,000 VA 402 A
LS 3V V 3 115,000
The base apparent power is S base 100 MVA , and the base line voltage on the secondary side is
V LS ,base 115 kV , so the base value of the secondary line current is
I LS ,base S base 100,000,000 VA 502 A
3V LS ,base V 3 115,000
so the per-unit secondary current is
I 402 A
I LS 1 cos 0.8 0.8 36.87
LS ,pu
I LS ,pu 502 A
The per-unit phasor diagram is shown below:
V P V 1.039 1.7 P
V = 1.00°
S
I 0.8 I = 0.8-31.8°
36.87
(b) The per-unit primary voltage of this transformer is
V V I 1.0 0 Z 36.87 0.8 0.015 j 0.06 1.039 1.7
P S EQ
and the voltage regulation is
1.039 1.0
VR 100% 3.9%
1.0
(c) The secondary side of this transfer is Y-connected, so the base phase voltage of the low voltage
(secondary) side of this transformer is:
V 115 kV
V S ,base LS ,base 66.4 kV
3 3
The base impedance of the transformer referred to the low-voltage side is:
3 V 2 3 66.4 kV 2
Z S ,base 133
base
S 100 MVA
base
Each per-unit impedance is converted to actual ohms referred to the low-voltage side by multiplying it by
this base impedance. The resulting equivalent circuit is shown below:
44