Page 51 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 51

2.00      j 7.98 



                              13.3 k                j 2.66 k







                               R  0.015 133         2.00 
                        EQ, S
                                   
                       X        0.06 13      7.98  3 
                        EQ, S
                                               
                       R   100 133    13.3  k
                        C
                                
                       X       20 133    2.66  k   
                        M
                 (d)  The per-unit losses in the series resistance are
                       P   EQ  I R EQ     0.8  2    0.015   0.0096 pu
                             2
                 and the actual losses in the series resistance are:

                       P   EQ  S base EQ ,pu    0.0096 pu 100 MVA  0.96 MW
                                P
                 The per-unit losses in the excitation branch are:
                                2    V   1.039  2
                       P EX ,pu             0.0108 pu
                              R EX    100
                 and the actual losses in the excitation branch are:

                       P   EX  base EX  ,pu     S  0.0108 pu    100 MVA   1.08 MW
                                P
                 The per-unit power supplied to the load
                              P      80 MW
                       P      load.           0.80 pu
                        load.pu
                              S base  100 MVA
                 Therefore, the transformer’s efficiency is
                          P                    0.80
                                                                   
                         OUT    100%                      100% 97.5%
                                                    
                                            
                           P IN        0.80 0.0096 0.0108
          2-12.  Three 20-kVA 24,000/277-V distribution transformers are connected in -Y.  The open-circuit test was
                 performed on the low-voltage side of this transformer bank, and the following data were recorded:
                      V line,OC   480  V    I line,OC    . 4  10 A       P 3,OC   945  W
                                                               
                 The short-circuit test was performed on the high-voltage side of this transformer bank, and the following
                 data were recorded:
                      V line, SC   1400 V      I line, SC    . 1  80  A       P 3,SC   912  W
                                                               
                 (a)  Find the per-unit equivalent circuit of this transformer bank.
                 (b)  Find the voltage regulation of this transformer bank at the rated load and 0.90 PF lagging.