Page 51 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 51
2.00 j 7.98
13.3 k j 2.66 k
R 0.015 133 2.00
EQ, S
X 0.06 13 7.98 3
EQ, S
R 100 133 13.3 k
C
X 20 133 2.66 k
M
(d) The per-unit losses in the series resistance are
P EQ I R EQ 0.8 2 0.015 0.0096 pu
2
and the actual losses in the series resistance are:
P EQ S base EQ ,pu 0.0096 pu 100 MVA 0.96 MW
P
The per-unit losses in the excitation branch are:
2 V 1.039 2
P EX ,pu 0.0108 pu
R EX 100
and the actual losses in the excitation branch are:
P EX base EX ,pu S 0.0108 pu 100 MVA 1.08 MW
P
The per-unit power supplied to the load
P 80 MW
P load. 0.80 pu
load.pu
S base 100 MVA
Therefore, the transformer’s efficiency is
P 0.80
OUT 100% 100% 97.5%
P IN 0.80 0.0096 0.0108
2-12. Three 20-kVA 24,000/277-V distribution transformers are connected in -Y. The open-circuit test was
performed on the low-voltage side of this transformer bank, and the following data were recorded:
V line,OC 480 V I line,OC . 4 10 A P 3,OC 945 W
The short-circuit test was performed on the high-voltage side of this transformer bank, and the following
data were recorded:
V line, SC 1400 V I line, SC . 1 80 A P 3,SC 912 W
(a) Find the per-unit equivalent circuit of this transformer bank.
(b) Find the voltage regulation of this transformer bank at the rated load and 0.90 PF lagging.
45