Page 77 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 77
Q G ,pu VI sin 0.4765 sin 41.6 0.316
1
S G ,pu VI 0.4765 0.4765
1
P G P G ,pu S base 0.356 1000 kVA 356 kW
Q G Q G ,pu S base 0.316 1000 kVA 316 kVAR
S S S 0.4765 1000 kVA 476.5 kVA
G G ,pu base
The power factor of the generator is
PF cos 41.6 0.748 lagging
(c) With the switch closed, the equivalent impedance of this circuit is
1.513 j 1.134 j 3.36
Z EQ 0.010 j 0.040 0.00723 j 0.0482 0.040 j 0.170 j 1.513 j 3.36 1.134
Z EQ 0.010 j 0.040 0.00788 j 0.0525 0.040 j 0.170 (2.358 j 0.109)
Z 2.415 j 0.367 2.443 8.65
EQ
The resulting current is
10
I 0.409 8.65
2.443 8.65
The load voltage under these conditions would be
V Z I 0.409 8.65 2.358 j 0.109 0.966 6.0
Load,pu Load
V Load V Load,pu base3 0.966 480 V 464 V
V
The power supplied to the two loads is the power supplied to the resistive component of the parallel
combination of the two loads: 2.358 pu.
2
2
P Load,pu I R Load 0.409 2.358 0.394
P P S 0.394 1000 kVA 394 kW
Load Load,pu base
The power supplied by the generator is
P G ,pu VI cos 0.409 cos6.0 0.407
1
1
Q G ,pu VI sin 0.409 sin6.0 0.0428
S VI 0.409 0.409
1
G ,pu
P G P G ,pu S base 0.407 1000 kVA 407 kW
Q G Q G ,pu S base 0.0428 1000 kVA 42.8 kVAR
S G S G ,pu S base 0.409 1000 kVA 409 kVA
The power factor of the generator is
PF cos 6.0 0.995 lagging
(d) The transmission losses with the switch open are:
2
2
P line,pu I R line 0.4765 0.00723 0.00164
P line P line ,pu S base 0.00164 1000 kVA 1.64 kW
The transmission losses with the switch closed are:
2
2
P line,pu I R line 0.409 0.00723 0.00121
71