Fieldbus 227






















                                                                                       I

                                                                       d
         Figure 13.34  Point-to-point mode; with provision for one 4-20  mA device and up to two masters, e.g., one management
         system and a hand-held terminal.










                                 Gateway             Bell 202-
                                                     Modem


          -------
           Process mana



                                        ir


           Field level






         Figure 13.35  With multi-drop mode, installation costs are considerably reduced. As manyas15field devices can be
         operated from one auxiliary power supply. Management systems and hand-held terminals can be used.

         can be used. Beyond this, distances up to 3000 m   Layer 2, the link layer, establishes the format
         can  be  covered  using  single,  shielded,  twisted   for  a  HART message.  HART  is  a  master/slave
         0.5 mm2 pairs.                           protocol. All the communication activities origin-
           A total resistance of between 230 0 and  1100 0   ate from a master,  e.g.,  a display terminal. This
         must be  available in the communication  circuit,   addresses a  field device (slave), which interprets
         as indicated in Figures 13.34 and 13.35 by Rg.   the command message and sends a response.