222  Microprocessor- based and intelligent transmitters



                                      p2
















            Figure 13.26  Measurement of  liquid level in a closed
            vessel, using two pressure transmitters.
            the data regarding the transmitter model and serial
            number, etc. However, it is important to remember
            that changes in the temperature of the stored liquid
            may lead to changes in density which, in turn, may
            result in an unacceptable loss of accuracy. A third
            transmitter  located at  a fixed distance above the
            bottom transmitter can be used to obtain the den-
            sity and make the necessary correction.


            13.9  Other microprocessor-
            based and intelligent
            measurement systems

            An  interesting  application  of  microprocessor-
            based  and  intelligent instrumentation  occurs  in
            the metering of natural gas. A typical example is
            the Spectra-Tek Flow Computer (see References),
            shown in Figure 13.27.
             The preferred method for fiscal metering of gas
            flow  is  by  the  measurement  of  the  differential
            pressure  across  an orifice plate.  The traditional   Figure 13.27  Spectra-Tek flow computer. Courtesy of
                                                     Spectra-Tek Ltd.
            approach  to achieve high  accuracy over a wide
            flow range has been to install several differential
            pressure  transmitters,  with  overlapping  ranges,   The Spectra-Tek Sentinel Flow Computer pro-
            across a single orifice plate,  as shown in Figure   vides the facilities to communicate digitally with
            13.28. With  the  improvements which have been   the transmitter. It can either use the transmitter’s
            made in the basic sensors and the introduction of   analog output, switching the range of  the trans-
            the smart transmitters, it has become possible to   mitter  as the  flow rate varies, or  it  can  use the
            use a single transmitter, the output from which is   digital  value  received  from  the  transmitter,  in
            a  conventional  4-20  mA  analog  signal with  the   which case no range  changing is necessary. The
            digital measurement signal superimposed on it.   unit  also provides similar facilities for  tempera-
             Taking the Honeywell ST3000 Model STD120,   ture  and  pressure  transmitters,  both  of  which
            the  reference  accuracy  for  the  digital  mode  is   could  be  “intelligent,”  and  it  also  accepts  the
            0.0625 percent of calibrated span or 0.125 percent   frequency signal from a gas density transmitter.
            of  reading  for  spans  between  62mbar  and   The  computer  calculates  the  mass  flow  rate
            1OOOmbar. This  means  that  the  transmitter  can   in accordance  with  IS0 5167, with temperature
            be  calibrated for the  differential pressure corres-   correction  for  pipe  and  orifice  bores.  Flowing
            ponding to the maximum flow rate and operated   density, standard density, and standard compress-
            over a wide range of flows, with optimal accuracy.   ibility  are  calculated  by  the  primary  method