Page 239 - Instrumentation Reference Book 3E
P. 239

Fieldbus 223









                                                       1  Stream





                                                             Mass FR
                                                             SVOL FR
                                                             Energy
                                                             Mass TOT


                                                             System alarm
                                                             Process alarm
                                                            Computer alarm


                                                             Printer
                                                             Supervisory
                                                            S-TEK supervisory
            Figure 13.28 Natural gas cost metering installation. Courtesyof Spectra-Tek Ltd.



            defined in AGA 8. using measured pressure and
            composition  data for up to 20 components. The
            calculated  standard  density  is  used  to  derive   13.10.1  Background
            standard volume. Calorific value is calculated in
            accordance  with  IS0 6976  using  the  measured   At  present,  the  majority  of  microprocessor-
            temperature, pressure, and gas composition data.   based  and  intelligent  transmitters  operate  in
            Calorific  value is  used to calculate  energy flow.   conventional  4420 mA  measurement  circuits,
            Mass,  standard  volume,  and  energy  are  each   but  it  is  inevitable  that  the  advantages  to  be
            available as a cumulative  total;  a daily total, as   gained  from  multiplexing  signals  from  sensors.
            well as the instantaneous flow rates. Analog out-   actuators,  and  controllers  will  be  a  feature  of
            puts  are  available  for  each  flow  rate  together   new  process  plants  as  well  as  plant  upgrading.
            with  an incremental  pulse output for mass flow   However.  to  implement  this,  a  commm  coin-
            rate.                                    munication  system,  or  fieldbus,  needs  to  be
              Three separate alarm outputs are provided  to   established.
            indicate  c'omputer alarm  (generated  by  internal   There  are  many  advantages  of  fieldbus  over
            diagnostic routines), system alarm (generated by   conventional analog systems. the most immediate
            a  fault  in  the  internal  or  external measurement   of  which  are  reduced  cost  of  installation  and
            circuits), and process alarms (generated  by  pro-   maintenance, increased flexibility, and enhanced
            cess  conditions  moving  out  of  limits).  These   functionaiity. such as self-diagnostics, calibration,
            hardwired  alarm outputs operate in conjunction   and condition monitoring. The  additional bene-
            with the flow computer's  front panel display and   fits  available  with  these  microprocessor-based
            may  be  connected  to  an  external  annunciator   and  intelligent  devices will  also  expand  the  use
            system.                                  of sensors and control systems.