Page 108 - Membranes for Industrial Wastewater Recovery and Re-Use
P. 108

Table 3.3  Summary of terms used to define flows through recirculating cooling towers
 Flow component   Definition   Flow rate, m'  h-'   Concentration of dissolved
                                     constituent(s). mg IF'
 Recirculating water   Flow rate of water that is recirculating in tower   QR   CR
 Blowdown   Flow rate of water deliberately removed from system   Qh   Ch = CR
 to limit salt build-up
 Evaporation   Water lost to atmosphere due to evaporation: -2%  of   Q,  = QTAT/700   c,  = 0
 recirculating water flow per 10°C temperature drop
 Drift   Water lost due to entrainment in wind. When salt or   Qd -0.2%  for old units;   Cd = CR
 brackish water is used, drift may contain high   Qd < 0.005% for efficient
 concentrations of salts and/or minerals that can deposit   designs
 on crops, soils, or structures
 Make-up water   Flowrate ofwater added to flow stream to replace water by   Qm  = Qe  + Qci + Qh + QL
 evaporation, drift and blowdown
 Other losses   Losses ofwater due to leaks   01.
 System capacity   Total volume of water in system   V
 Temperature differential   Difference between average water temperature following   AT=T,"o,,-T,,,",,,,"C
 evaporation and average water temperature returning to
 tower
 Cycle time   Time required for water to travel around circulating loop   t, = V/QR
 Holding time index   The half-life of chemicals added to the system   tli2=(ln2)xVx(Rc-
             1)/E