Page 177 - Modern Control of DC-Based Power Systems
P. 177

Control Approaches for Parallel Source Converter Systems     141




                        I
                    V bus,  Lk, I CPL       Target   Implicit   Calculation of
                                            definiton of
                                system                    the duty cycle
                                           the manifold

                           Measurement       Plant:         Control signal
                                        generators and loads

              Figure 5.16 Structure of the proposed I&I control.

              previously explained for all the generation-side converters. The load is
              characterized by a resistance and an ideal CPL and it is connected to the
              same bus where all the converters are connected [11].
                 The buck converter is controlled by means of the control law
              described in (5.89) where x 1 5 V 2 V and x 2 5 I L;k , where k 5 1; .. . ; 3

                                           ref
              represents the measurement of the inductor current of the converter k.
                 The current sharing among the buck converters is controlled by the
              droop characteristic described by:

                                                                         (5.90)
                                     V 5 V ref 2 r d UI L;k
                                       ref
                 The control of the sharing is obtained by changing the value of the
              fictitious resistance [30].
                 The current measurement of the CPL is shared among the four buck
              converters and multiplied by a factor that reduces the impact of the CPL
              current on the calculation of the control output, given that the values in
              p.u. of the CPL current are very high compared to the other variables.
                 The overall control structure of the parallel-connected system is
              described by Fig. 5.17.
                 Fig. 5.17 demonstrates that the proposed control approach for the
              parallel-connected converters exhibits a centralized configuration, given
              that the CPL current must be shared among the different controllers.


              5.3.4 Simulation Results
              5.3.4.1 Cascaded System
              A cascaded converter setup has been modeled in Matlab-SIMULINK
              with the parameters described in Table 6.1. In the simulation, a step vari-
              ation of the CPL load has been performed. The variation of the bus volt-
              age during the step change of the CPL load is described in Fig. 5.18.At
              t 5 0.25 s the load step of 7.5 MW was performed, demonstrating that
   172   173   174   175   176   177   178   179   180   181   182