Page 234 - Modern Control of DC-Based Power Systems
P. 234

198                                 Modern Control of DC-Based Power Systems






















          Figure 5.62 ISPS V bus H N for ideal CPL   Step 30.9 - 53.4 MW.






















          Figure 5.63 I L15L25L3 H N for ideal CPL and 30.9 - 53.4 MW.


          22.5 MW is applied at the load side at t 5 0.25 s. The effect of the
          increasing and decreasing of the CPL load on the load voltage is described
          in Fig. 5.62, demonstrating that the voltage remains stable and reaches the
          voltage set-points that are gradually modified by the action of the droop
          control. In Fig. 5.62 one can observe the transient for the current
          (Fig. 5.63).

          5.7.6.3 Impact of Measurement Noise
          In this scenario, the robustness properties of the controller are presented.
          Pink noise corrupts the measurement of each primary controller. A band