Control Approaches for Parallel Source Converter Systems     197






















              Figure 5.60 Voltage H N cascaded   Ideal CPL   Step 10.3 - 17.8 MW.























              Figure 5.61 Current H N cascaded   Ideal CPL   Step 10.3 - 17.8 MW.



              manner. We are interested in observing how the H N controller behaves
              when a nonlinear load such an ideal CPL is introduced into the system.
              Additionally, the impact of measurement uncertainties is tested to observe
              robustness properties. The droop resistances are set equal to provide equal
              voltage references to the primary controller. A voltage drop of 0.3 p.u at
              full load was considered while designing the droop controller. This value
              provides sufficient resolution in primary voltage references at low loads to
              prevent improper current sharing and at the same time, furthermore the
              drop does not create instability at peak loads. A load step increase of