Page 230 - Pipeline Rules of Thumb Handbook
P. 230

Corrosion/Coatings  217

           current that can be collected by the pipeline without exceed-  can be applied along the pipeline from A to C and from
           ing the disbonding limit. The lower limit is the minimum  D to F.
           amount of current that can be collected by the pipeline to  When the earth current can reverse polarity, as with the
           keep it above the corrosion limit.                    Pacific Northwest (PNW)-Pacific Southwest (PSW) intertie,
             At this value of HVDC (Figure 4), the uncorrected pipeline  then the same process that was used to develop the limits
           effect is shown by Curve 1. No protection is needed along  shown in Figure 4 can be repeated for the opposite HVDC
           either end of the pipeline in Regions A-B or E-F. Corrosion  polarity. The limits on protection along the pipeline when the
           protection is needed between B and E. The minimum pro-  HVDC electrode is discharging current, at its maximum
           tection effect along the line is shown by Curve 2. The resul-  value, into the earth are shown in Figure 5.
           tant of the HVDC and this protection effect lies on the  The combination of these two sets of limiting characteris-
           corrosion limit. The maximum protective effect that can be  tics is shown in Figure 6. The graph shows the length along
           applied along the line, without exceeding the coating dis-  the pipeline where a fixed level of cathodic protection can
           bonding limit, is shown by Curve 3. Under this maximum  be used and those regions where controlled protection is
           value and polarity of HVDC current, the region between  required for any value of HVDC earth current. In this
           these two protective limits, therefore, defines the range of  particular example, variable protection is required along the
           acceptable protective system performance at any location on  pipeline for approximately 20 to 30 miles on either side of
           the pipeline.                                         the point closest to the HVDC electrode. Cathodic protec-
             When the HVDC effect decreases, due to a reduction in  tion is required when the HVDC electrode is collecting
           the ground current, the required level of protection on the  current from the earth. That is, the HVDC component of
           line also decreases. Along the pipeline length from C to D,  current, conducted by the pipeline, is discharging from the
           the protection must be reduced to avoid exceeding the dis-  line near the earth electrode. The required protective current
           bonding limit. At zero HVDC effect, the protective system  along the pipeline to counteract the HVDC effect under this
           effect must fall between the corrosion and disbonding limits  condition is show as Region 1 in Figure 6.
           all along the line.                                     When the HVDC polarity is reversed and the magnitude
             Examination of the limits for these two values of HVDC  of the ground current is increased to the maximum value, a
           system operation shows that the protective effect must be  different problem is encountered. The electric field which is
           varied in response to the HVDC effect over the length of the  established around the electrode and pipeline causes current
           pipeline from C to D: automatic regulation of the protective  to enter the pipeline through the coating. In this example, the
           current is needed over this length of the pipeline. With   disbonding limit is exceeded over the length of the pipeline
           only this polarity of HVDC current, a fixed level of protection  from C to D at the maximum value of HVDC earth current.
































                                                                           Figure 5. Limits on protection along the pipeline
                                                                           when the HVDC electrode is discharging current,
                                                                           at its maximum value, into the earth.
   225   226   227   228   229   230   231   232   233   234   235