Page 338 - Power Electronic Control in Electrical Systems
P. 338

//SYS21/F:/PEC/REVISES_10-11-01/075065126-CH008.3D ± 326 ± [290±372/83] 17.11.2001 10:29AM







               326 Transient studies of FACTS and Custom Power equipment






                                       Line voltage
                                                      STATCOM voltage  Output current
















                      Fig. 8.42 Output voltage and current waveforms for a 48-pulse STATCOM generating reactive power.




                      configuration. The eight-inverter poles comprising sixteen GTO valves, depicted
                      symbolically, are associated with one of the three output phases the STATCOM
                      generates. Each inverter pole produces a square voltage waveform, progressively
                      phase-shifted from one pole to the next by an appropriately chosen angle. These
                      eight square-wave pole voltages are combined by magnetic summing circuits into two
                      voltage waveforms displaced by 30 . One of these waveforms feeds the wye and the

                      other the delta secondary of the main coupling transformer. The final 48-pulse
                      output voltage waveform is obtained at the transformer primary. The voltage and
                      current output waveforms are shown in Figure 8.42 (Schauder, 1997).
                        A simplified block diagram of the control system used for the 48-pulse STATCOM
                      is shown in Figure 8.43. An inner feedback loop is used to regulate the STATCOM
                      instantaneous reactive current. Note that this control is achieved by varying the
                      phase angle a, of the inverter output voltage relative to the transmission line voltage.
                      This technique makes it possible to maintain a constant maximum ratio between the
                      converter output voltage and the DC capacitor voltage. The reference value for the
                      reactive current control loop is generated by an outer loop responsible for the system
                      voltage control. This outer control loop is similar to that used in conventional static
                      var compensators, and includes an adjustable slope setting that defines the voltage
                      error at full STATCOM reactive output.
                        A simple example is presented in this section where a 12-pulse STATCOM is
                      implemented in PSCAD/EMTDC to illustrate the waveforms generated by the
                      multipulse topology. The circuit used for this purpose is shown in Figure 8.44. The
                      PSCAD/EMTDC implementations of this circuit and the switching controller are
                      shown in Figures 8.45 and 8.46 respectively.
                        Figure 8.47 shows the output voltage and current waveforms generated by the 12-
                      pulse VSC-based STATCOM of the example.
   333   334   335   336   337   338   339   340   341   342   343