Page 156 - Power Electronics Handbook
P. 156

A.C. contactors   149

                   non-conducting the load is effectively isolated from the supply lines A and
                   B, if the leakage of the devices is ignored. When thyristors 1 and 2 are fired
                   they can be considered as short circuits and the load is connected to the
                   supply.
                     Figure 7.l(b) shows a three-phase static contactor. Only one thyristor
                   and a reverse diode is required in each line, since one of  the lines must
                   conduct in the forward direction before any load current can flow. As in
                   single-phase contactors, with no thyristor gate drive the load is isolated or
                   off, and when the thyristors are turned on the load is connected to the
                   supply.
                     If  it is required to reverse the supply to the load, for instance where the
                   load is a motor and its direction of  rotation is to be changed, the circuit of
                   Figure 7.l(c) must be used. With thyristors 1 to 6 conducting and thyristors
                   7 to 10  off, line A feeds E, B feeds F and C feeds G. To reverse the supply
                   to the load, thyristors 1,2 and 7 to 10 are on and thyristors 3 to 6 are off.
                   Now  A  feeds  E, B feeds  G and  C feeds  F. It  is  necessary  to  use
                   back-to-back thyristors, or triacs, in all the lines since if, for instance, 10
                   was a diode then firing thyristor 3 would cause a short circuit across lines B
                   and C.
                     The devices in Figure 7.1 must  all be rated to withstand the peak line
                   voltage. For 240 V single-phase and 440 V three-phase supplies this means
                   peak voltages of 34OV and 63OV respectively. To allow for line transients
                   it  is  usual  to  employ  MOV  and  8OOV  devices.  Additionally,  surge
                   suppressors must be used between lines and across devices if the transients
                   are troublesome. In this context it is perhaps worth noting that the circuit
                   of  Figure  7.l(b)  is  protected against reverse  voltage  transients by  the
                   diodes. Overvoltage in the forward direction could cause a thyristor to
                   break over  into  conduction  for  a  half  cycle,  but  now  it  need  not  be
                   damaged and the load may be such as not to be appreciably affected by the
                   half cycle of power.
                     The  current rating  of  the  devices can be  calculated as follows, with
                   reference to the single-phase circuit. Assuming the line current to the load
                   to be given by Z,,&ne when the thyristors are conducting, then the r.m.s.
                   line current is given by equation (7.1).





                            IPk
                         =-
                            J2
                     The thyristors carry current for only half  a cycle each, so their mean
                   rating is given by IT(.v,  in  equation (7.2), and this can be simplified to
                   equation (7.3) by  using equation (7.1).





                             1Pk
                           =-                                                  (7.2)
                              n
   151   152   153   154   155   156   157   158   159   160   161