Page 169 - Power Quality in Electrical Systems
P. 169

Dynamic Voltage Compensators  151

        Operation on ITIC curve
        With a relatively limited range of operation, the dynamic voltage com-
        pensator (without energy storage) can protect loads for a majority of
        voltage sags that fall outside the “acceptable” region of the CBEMA or
        ITIC curves. The operation of a commercial dynamic voltage compen-
        sator is superimposed on the ITIC and CBEMA curves in Figure 10.5
        [10.4]. The scatter plot of sags below the ITIC curve (dashed lines) fall
        into the region covered by the compensator. The commercial compen-
        sator utilizes the parallel circuit of Figure 10.2 for single-phase opera-
        tion and the series circuit of Figure 10.3 for higher power three-phase
        operation up to 500 kVA [10.4]. This particular compensator can provide
        a 100 percent boost of the source voltage for a time up to 0.2 s (12.4 cycles),
        and a 50 percent boost up to 2 s (124 cycles). The compensator utilizes
        the energy supplied from the line or stored in the dc-link capacitors. For
        a 50-percent boost, the capacitors require 60 s to recharge before the com-
        pensator can handle another sag of time duration up to 2 s.
          Longer times of operation than that shown in Figure 10.5 require
        energy storage—for example, batteries—in the dc link. At some sag
        time duration, a battery-powered UPS provides a better solution for
        the power-quality problem. The UPS can handle both short time and
        extended time outages. A comparison of the dynamic voltage compen-
        sator and the UPS is given in reference [10.5], and also shown in the
        table of Figure 10.6 [10.4].




                              Magnitude versus duration scatter plot
           150
                                                           Total events: 301
                                                          Events below: 238
                                                          Events above: 63
           125                                           Below CBEMA: 110
          Voltage magnitude (%)  100
                                                         Above CBEMA: 61
            75

            50

            25
                             DySC protected
             0
              10 –1      10 0       10 1        10 2       10 3       10 4
                                     Duration (Cycles)
        Figure 10.5 Scatter plot of PQ events at one industrial site over 2.3 years, overlaid with
        the CBEMA curve (solid thin lines), the ITIC curve (dashed lines), and the single-phase
        compensator (DySC) protection regime (thick lines) [10.4].
        [© 2001, IEEE, reprinted with permission]
   164   165   166   167   168   169   170   171   172   173   174