Page 212 - Power Quality in Electrical Systems
P. 212

194   Chapter Thirteen


        Normal                        Alternate
         source                        source
                   Static transfer switch


              CB                     CB



                              Manual
                              bypass
                            CB

                              Utility transf.




                                      Main bus




             Non-crit     By
              load                  UPS       Bat.
                         pass



                                       UPS bus


                              Load
        Figure 13.6 Two primary-voltage utility feeders with static
        transfer switch.


        5. UPS plus Two Feeders and a Utility Transfer Switch: An ele-
           mentary standby power system utilizing two utility feeders from two
           substations is shown in Figure 13.6. In case of a feeder fault or fail-
           ure, the utility transfer switch transfers the service to the alternate
           feeder. The UPS operates from its battery during the transition.
           Other loads, such as air conditioning, heating, and lighting, either
           continue to operate or must be restarted.

        Engine-Generator Sets
        Engine-generator sets (E/G sets) are used in standby power systems to
        extend the operation time of the UPS beyond the available discharge
        time of the batteries. For large UPSs (for example, larger than 100 kVA),