Page 94 - Practical Machinery Management for Process Plants Major Process Equipment Maintenance and Repair
P. 94

Installation, Maintenance, and Repair of  Vertical Pumps   79

                  An alternate method to set semi-open impellers is:

                    1.  Raise the rotor as high as it will go, then lower it two turns on the
                       adjusting nut. While raising the rotor, do not use excessive force.
                       Especially if the impellers are collet mounted, be sure that they are
                       not pushed downward. Just raise the rotor until a very slight drag is
                       detected when the shaft is rotated.

                    2.  Lock the adjusting nut, start the pump, record the ammeter reading
                       with the pump running at or near shutoff or at the minimum flow
                       allowed by the system.

                    3.  Check to be sure that the ammeter reading is less than the amps on
                       the motor nameplate.

                    4.  Lower the rotor  1/12  turn, lock the adjusting nut, start the pump,
                       record the ammeter reading with the pump running at or near shut-
                       off or at the minimum flow allowed by the system.

                    5.  Repeat Step 4 until the ammeter reading increases sharply because
                       the impellers are rubbing on the bowls.

                    6.  Raise the rotor  1/12 turn to its final position and lock the adjusting
                       nut.



                              Hollow Shaft Driver Reverse Protection Clutch
                    If  the driver is accidentally run  with  reverse rotation, the deepwell
                  pump shaft couplings may unscrew and cause damage. Figure 2-9 shows
                  a  reverse protection clutch  which  automatically disengages the pump
                  shaft from the driver if this occurs. In some shallow settings, particularly
                  with closed impellers, the pump may develop a momentary upthrust dur-
                  ing start-up. In these installations, it is necessary to install hold-down
                  bolts in the clutch and to check that the driver thrust bearing is locked
                  against upthrust.
                  Hollow Shaft Driver Nonreverse Ratchet

                    If the foot valve or check valve fails in a deepwell pump installation,
                  when the driver is de-energized the water will run back down the dis-
                  charge column, and the pump will act as an unloaded turbine and achieve
                  a reverse rotation that can reach rather high speed. The torque does not
                  reverse, so the threaded couplings do not unscrew as a result. Although
   89   90   91   92   93   94   95   96   97   98   99