282  Practical Power System and Protective Relays Commissioning


               Set to 1.5 for residential loads;
               F 5 reset ratio 5 0.85 for electromechanical relays and set to 0.9 0.95
               for static and digital relays;
               I L Max 5 maximum expected load;
               I set 5 2 2.5 I L Max .
               The performance of overcurrent relays is checked by calculating the
            sensitivity factor, S, which is the ratio of the minimum short circuit current
            following at the relay in the end protected line in a radial system to the relay
            setting as follows:
                            S 5 I sc minimum=I set should be . 1:5


            19.1.2 TRANSMISSION LINE OVERCURRENT PROTECTION

            Fig. 19.1.1 illustrates the overcurrent protection of a high-voltage transmis-
            sion line
               The circuit data include:
               Overcurrent relay type MCGG22.
               Application:
               Backup protection 500 kV, fault level at end B 5 12,000 MVA, current
            setting of relay at A 5 800 A.
               I s 5 800 A  current transformer (CT) ratio 5  1600
                                                     1
                                           1
                                   I s 5 800   5 0:5A
                                          1600
               Plug setting multiplier (PSM)

                                        I f     MVA F
                                 PSM 5   -I F 5
                                        I s     O3 3 V
                                     12; 000
                                I F 5        5 13:856 KA
                                    O3 3 500















            FIGURE 19.1.1 Overcurrent protection of a high-voltage transmission line.