Protection Relays Settings Chapter | 19  285


             Subchapter 19.2


             Feeder Backup Overcurrent Protections

             19.2.1 INTRODUCTION

             Overcurrent protection here is used as backup protection, with a considerable
             time delay, which means it works as a second line of defense to protect the
             line if the main or primary protection fails to isolate the line for the fault
             instantaneously.


             19.2.2 WORKED EXAMPLE
             Fig. 19.2.1 gives an example of line backup overcurrent protection.
                Line AB 500 kV maximum load current 5 I L Max 5 1200 A
                For OC relay at A (R):
                I set 5 1.2 3 I L Max
                5 1.2 3  1200  5 1.44 A
                       1000
                PSM calculation:
                                        I F       MVA F
                                 PSM 5    andI F 5
                                        I S      O3 3 V
                                 I F 5 80 KA
                                 I S 5 1200 A
                                        80; 000
                                 PSM 5        5 80
                                         1000
                Using a standard inverse curve of the OC relay we then have:

                                     0:14      0:14
                              T R 5        5         5 1:528
                                  PSM 0:0221  80 0:0221
             where T R 5 relay operation time assuming that the relay will operates on
             1 second for this fault then t.operation 5 TM.T R , where TM 5 time
             multiplier.













             FIGURE 19.2.1 Line backup overcurrent protection.