Page 293 - Practical Power System and Protective Relays Commissioning
P. 293

Protection Relays Settings Chapter | 19  287


                                          29:3 3 10 3
                                     I F
                              PSM 5    5           5 36:625
                                     I S     800
                Assuming that the relay will operates on 1 second for a fault on end B:
                     t:operation
                TM 5
                         T R
                                     0:14      0:14
                              T R 5        5         5 1:884
                                  PSM 0:0221  36 0:0221
                                           1
                                    TM 5       5 0:530
                                         1:884
                Relay setting:
                I set 5 800 A
                5 0.8 A secondary
                PSM 5 36  TM 5 0.53
                                0:14
                t:operation 5 0:53  0:0221
                               36
                5 0.998 second



             Subchapter 19.3


             Feeder Unit Differential Protection


             19.3.1 INTRODUCTION
             This protection is used to protect overhead transmission lines and is
             commonly used as main 2 in utilities. The disadvantage of this protec-
             tion is the blind zone, which is not protected by this protection—this
             means the zone between the circuit breaker (CB) and the current
             transformer in one end—as this zone is protected by backup protections
             (Fig. 19.3.1).















             FIGURE 19.3.1 Line differential protection.