Page 295 - Practical Power System and Protective Relays Commissioning
P. 295

Protection Relays Settings Chapter | 19  289


             Subchapter 19.4


             Setting of Distance Protection

             19.4.1 INTRODUCTION

             Distance protection is widely used as the main protection—primary
             protection—in overhead transmission lines and has the advantage that it
             gives backup protection for adjacent lines. However, it has the disadvantage
             that it does not have accurate measurements for close-up faults near the
             remote end of the line due to the errors in CT and PT measurements and the
             transient nature of the short circuit current, also due to the tower arc fault
             resistance—what we call distance protection overreaching and underreach-
             ing—that it is not accurate in measurement in short transmission lines due to
             the effect of the system impedance ratio.

             19.4.2 WORKED EXAMPLES
             Worked example 1
                Most distance protection is set to have three zones and one backup start zone.
                The setting of the first zone is as follows for a relay at end A:
                Z 1 5 0.85 Z L , t 1 5 0 instantaneously
                where Z L 5 line impedance.
                Setting of the second step zone 2 is as follows for a relay at end A
             (Fig. 19.4.1):
                The Z 2 setting is the lower value of the following:

                                           ð
                                  Z 2 5 0:85 Z L11 0:85 Z L2 Þ
                                           ð
                                  Z 2 5 0:85 Z L1 1 Z T Þ


















             FIGURE 19.4.1 Distance protection application setting: Example 1.
   290   291   292   293   294   295   296   297   298   299   300