288  Practical Power System and Protective Relays Commissioning


            19.3.2 WORKED EXAMPLE
            Worked example:
               Line A B 500 kV B 5 1.877 CT 5 1200/1 at both sides choose the relay
            characteristic shown in Fig. 19.3.2


















            FIGURE 19.3.2 Line differential protection characteristic.

                     j
               j I diff j 5 I A 1 I B j
                         j ½
               j I bias j 5 0:5 I A1 1 I B1 jŠ
                                   B 3 1000
               Line charging current 5
                                    V 3 O3
                                         1:877 3 1000
                                    I ch 5
                                          500 3 O3
               5 2.167 A
                               I set min 5 2:5 3 2:167 5 5:4175 A
               I set 5 0.2 I N
                                 I set 5 0:2 3 1200 5 240 A

               I set . 2.5 I ch
               I S1 5 240 A primary
                                        240
                                   I S1 5   5 0:2A
                                        1200
                                   I S2 5 2I N
                                   5 2 3 1200 5 2400 A
                                I S2 5 2400 A primary
                                     2400
                                I S2 5    5 2 A secondary
                                     1200
                                K 1 2 slop1 5 30 %
                                K 2 2 slop2 5 150 %